2 Mounting
22
V1.00/EN/00741192/2021-03-30 [IPC 300]
2.3.1 Admissible load current depending on the site altitude
Site altitude
In the case of air cooling, it must be noted that the effectiveness of the cooling
is reduced as the site altitude increases. As a result, the ampacity of the
IPC 300 decreases as the site altitude increases, as shown in the diagram.
1000
2000
40
20
100
site altitude in m
above sea level
80
Ampacity in %
91,4%
60
3000
4000
5000
Reduction over 1000m above sea level: 0,86 %/100m
A
Destruction through overheating:
In the event of operation at maximum load current over an extended period,
the heat sink and its surroundings heat up.
The device temperature must not exceed 100 °C.
At a device temperature of >100 °C, the message "Warning - high tempera-
ture" is displayed.
At a device temperature of >105 °C, the output level is gradually reduced by
10 % each time the temperature increases by one degree.
At a device temperature of >115 °C, the power controller is completely
switched off.
v
Summary of Contents for 709051
Page 8: ...8 V1 00 EN 00741192 2021 03 30 IPC 300 Contents...
Page 26: ...2 Mounting 26 V1 00 EN 00741192 2021 03 30 IPC 300...
Page 48: ...4 Operation 48 V1 00 EN 00741192 2021 03 30 IPC 300...
Page 62: ...5 Configuration 62 V1 00 EN 00741192 2021 03 30 IPC 300...
Page 76: ...6 Special device functions 76 V1 00 EN 00741192 2021 03 30 IPC 300...
Page 84: ...8 Error messages and alarms 84 V1 00 EN 00741192 2021 03 30 IPC 300...
Page 90: ...10 Technical data 90 V1 00 EN 00741192 2021 03 30 IPC 300...
Page 91: ...V1 00 EN 00741192 2021 03 30 IPC 300 91 11 Certificate 11 1 China RoHS...