V1.00/EN/00741192/2021-03-30 [IPC 300]
73
6 Special device functions
For this OK state, an average value is saved in the IPC 300. This value is mon-
itored with a tolerance range of
±
10 %. This serves to compensate for small
imbalances in the load.
If a load changes in a strand so that it goes beyond the tolerance range, the
remaining load elements are at risk as they are subject to too high a current.
The IPC 300 reacts to this by reporting a load failure in the strand affected.
This means the customer is able to detect the faulty load element and replace
it.
For this, it is recommended you configure the power reduction as described in
the following:
Config.level
r
Ext.current sensors
r
Ext.current sensor2
r
Power reduction
The power reduction activated in this manner automatically reacts when the tol-
erance range around the average value described above is no longer complied
with (load change).
The IPC 300 reduces the power in line with the extent of the load change, there-
by protecting the remaining load elements until the component is replaced.
Summary of Contents for 709051
Page 8: ...8 V1 00 EN 00741192 2021 03 30 IPC 300 Contents...
Page 26: ...2 Mounting 26 V1 00 EN 00741192 2021 03 30 IPC 300...
Page 48: ...4 Operation 48 V1 00 EN 00741192 2021 03 30 IPC 300...
Page 62: ...5 Configuration 62 V1 00 EN 00741192 2021 03 30 IPC 300...
Page 76: ...6 Special device functions 76 V1 00 EN 00741192 2021 03 30 IPC 300...
Page 84: ...8 Error messages and alarms 84 V1 00 EN 00741192 2021 03 30 IPC 300...
Page 90: ...10 Technical data 90 V1 00 EN 00741192 2021 03 30 IPC 300...
Page 91: ...V1 00 EN 00741192 2021 03 30 IPC 300 91 11 Certificate 11 1 China RoHS...