5 Configuration
60
V1.00/EN/00741192/2021-03-30 [IPC 300]
5.1.9
Analog output
Different internal values can be output as a standard signal at the analog out-
put.
5.1.10 RS422/485
Interface parameters for RS422/485 (see interface description)
Value / settings
Description
Signal type
This setting specifies the standard signal that should be out-
put.
Switched off
Output does not emit signal.
0 to 20 mA
Output emits the "Value to be output" in the form of a current
signal.
4 to 20 mA
0 to 10 V
Output emits the "Value to be output" in the form of a voltage
signal.
2 to 10 V
0 to 5 V
1 to 5 V
Value to be output
This setting involves the selection of the value that should be
output at the analog output.
Load voltage
Example:
The load voltage can vary between 0 and 380 V depending on
the device type.
As the signal range is set per default to 0 to 9999.9, the end
value must be adjusted to 380.0 to make use of the full signal
range.
Note:
Load voltage
2
= load voltage squared
Load current
2
= load current squared
Load voltage
2
Load current
Load current
2
Power (in W)
Power (in kW)
Load resistance
DC intermediate cir-
cuit voltage
Device temperature
Setpoint value
Signal range start
value
0 to 9999.9
Lower limit for the "Value to be output"
Signal range end
value
0 to 9999.9
Upper limit for the "Value to be output"
k
/ bold = default setting
Value / settings
Description
Baud rate
9600
19200
38400
Data format
8-1-none
Data bits-stop bits-parity check
8-1-odd
8-1-even
8-2-none
Device address
0 to 1 to 255
According to Modbus specification, the address 0 is actually
not permitted. In the IPC 300 it is used to switch off the signal-
ing of a bus error.
Therefore if the power controller has an RS422/485 interface,
and this is not connected to an active bus, you can suppress
the "bus error" error message by changing the address to 0.
Summary of Contents for 709051
Page 8: ...8 V1 00 EN 00741192 2021 03 30 IPC 300 Contents...
Page 26: ...2 Mounting 26 V1 00 EN 00741192 2021 03 30 IPC 300...
Page 48: ...4 Operation 48 V1 00 EN 00741192 2021 03 30 IPC 300...
Page 62: ...5 Configuration 62 V1 00 EN 00741192 2021 03 30 IPC 300...
Page 76: ...6 Special device functions 76 V1 00 EN 00741192 2021 03 30 IPC 300...
Page 84: ...8 Error messages and alarms 84 V1 00 EN 00741192 2021 03 30 IPC 300...
Page 90: ...10 Technical data 90 V1 00 EN 00741192 2021 03 30 IPC 300...
Page 91: ...V1 00 EN 00741192 2021 03 30 IPC 300 91 11 Certificate 11 1 China RoHS...