UMG 96RM-PN
~
~
Group 2
Group 1
Fig. Connection
of digital/pulse
outputs
Digital outputs
These outputs are galvanically separated from
the analysis electronics using optocouplers. The digital
outputs have a common supply.
• The digital outputs of group 1 can switch AC and DC
loads. The digital outputs of group 2 can
not switch
AC loads.
• The digital outputs are
not short-circuit proof.
• Connected cables that are longer than 30m must be
shielded when laid.
• An external auxiliary voltage is required.
• The digital outputs
of Group 1 can be used as pulse
outputs.
• The digital outputs can be controlled via Modbus and
ProfiNet.
• The digital outputs
of Group 1 can output results of
comparators.