112
UMG 96RM-PN
Table 2 - Modbus address list
(often needed measured values)
19000
808
float
RD
V
Voltage L1-N
19002
810
float
RD
V
Voltage L2-N
19004
812
float
RD
V
Voltage L3-N
19006
814
float
RD
V
Voltage L1-L2
19008
816
float
RD
V
Voltage L2-L3
19010
818
float
RD
V
Voltage L3-L1
19012
860
float
RD
A
Current, L1
19014
862
float
RD
A
Current, L2
19016
864
float
RD
A
Current, L3
19018
866
float
RD
A
Vector sum; IN=I1+I2+I3
19020
868
float
RD
W
Effective power L1
19022
870
float
RD
W
Effective power L2
19024
872
float
RD
W
Effective power L3
19026
874
float
RD
W
Sum; Psum3=P1+P2+P3
19028
884
float
RD
VA
Apparent power S L1
19030
886
float
RD
VA
Apparent power S L2
Modbus Address
Address
on display
Format
RD/WR
Unit
Comment
C
The addresses listed in this documentation
within the range 0-800 can be set directly
on the device.
The address range 800-999 is available
for the programming of comparators on
the device. The addresses in the range
of 1000 and above can only be edited via
Modbus!
C
A complete overview of the parameters and
measured values as well as explanations
on selected measured values can be found
in the document "Modbus Address List",
which can be found on the CD or online.