70
UMG 96RM-PN
Failure monitoring (RCM) for I5, I6
The UMG96RM-PN enables continuous monitoring of
the connection to the residual current transformer on
inputs I5 and I6.
Modbus addr. Value / Function
553 (I5)
554 (I6)
0 = Transformer monitoring, I5 and I6
deactivated
1 = Transformer monitoring, I5 and I6
activated
If there is an interruption in the connection to the current
transformer, this state is recorded in certain registers or
indicated in the GridVis software:
Modbus addr. Value / Function
10014 (I5)
10015 (I6)
0 = Connection of the residual current
transformer to I5 and I6 error-free
1 = Error in the current transformer
connection to I5 and I6
m
The monitoring of the connection to
the residual current transformer is only
available in the AC mode!
Residual current transformers of Type A
must be used for transformer monitoring!
We recommend configuring the residual
current measurement settings in GridVis.