UMG 96RM-PN
Address
Format
RD/WR
Unit
Comment
Setting range
Default
*1 0 =Comparator group, 1=Pulse output, 2=Value from an external source (Modbus), 3=Reserved, 4=Reserved, 5=ProfiNet
*2 0=Not inverted, 1=Inverted *3 0 = No measurement of the current or voltage path. *4 The setting 8 is equal setting 0.
145
SHORT
RD/WR
-
"Flash display"
0-3
0
Bit 1 = 1/0: active/inactive for
Comparator group output 1
Bit 2 = 1/0: active/inactive for
Comparator group output 2
200
SHORT
RD/WR
-
Selection of source for
Digital output 1
0 - 5
*1
1
201
SHORT
RD/WR
-
Inverter Digital output 1
0, 1
*2
0
202
SHORT
RD/WR
-
Selection of source for
Digital output 2
0 - 5
*1
1
203
SHORT
RD/WR
-
Inverter Digital output 2
0, 1
*2
0
500
SHORT
RD/WR
-
Terminal assignment, I L1
-3 to 0 to +3
3)
+1
501
SHORT
RD/WR
-
Terminal assignment, I L2
-3 to 0 to +3
3)
+2
502
SHORT
RD/WR
-
Terminal assignment, I L3
-3 to 0 to +3
3)
+3
503
SHORT
RD/WR
-
Terminal assignment, U L1
0 - 3
3)
1
504
SHORT
RD/WR
-
Terminal assignment, U L2
0 - 3
3)
2
505
SHORT
RD/WR
-
Terminal assignment, U L3
0 - 3
3)
3
506
SHORT
RD/WR
-
Clear min and max values
0 - 1
0
507
SHORT
RD/WR
-
Clear energy counter
0 - 1
0
508
SHORT
RD/WR
-
Force write to EEPROM
0 - 1
0
Note: Energy values and min/max values are written to the EEPROM every 5 minutes.
509
SHORT
RD/WR
-
Connection diagram, voltage
0 - 8
4)
0
510
SHORT
RD/WR
-
Connection diagram, current
0 - 8
0
511
SHORT
RD/WR
-
Relevant voltage for THD and FFT
0,
1
0
In the display, the voltages can be displayed for THD and FFT as L-N or as L-L values. 0=LN, 1=LL