49
UMG 96RM-PN
Configuration
Connecting the supply voltage
The supply voltage must be connected for the
configuration of the UMG 96RM-PN.
The supply voltage level for the UMG 96RM-PN is
specified on the rating plate.
If no screen appears, check whether the supply voltage
is within the rated voltage range.
Current and voltage transformer
A current transformer of 5/5A is set in factory. Only if
voltage transformers are connected does the pre-
programmed voltage transformer ratio need modifying.
When connecting voltage transformers, pay attention
to the measured voltage specified on the rating plate of
the UMG 96RM-PN!
c
Attention!
If the supply voltage does not correspond
to the voltage indicated on the rating plate,
this may lead to malfunctions and severe
damage to the device.
C
The adjustable value 0 for the primary
current transformer does not produce any
meaningful work values, and must not be
used.
m
Devices based on automatic frequency
detection require approx. 5 seconds to
determine the mains frequency. During this
time, the measured values do not comply
with the promised measurement uncertainty.
C
Prior to commissioning potential produc-
tion dependant contents of the energy
counter and min/max values have to be
deleted.