86
UMG 96RM-PN
• Measured value (addr. 110,116,122,129,135,141)
The measured value contains the address of
the measured value to be monitored.
Measured value = 0 the comparator is inactive.
• Threshold value (addr. 108,114,120,127,133,139)
The threshold value is where you write the value to be
compared with the measured value.
• Min. switch-on time (addr. 111,117,123,130,136,142)
The logic operation result (e.g. Addr. 610) is retained
for the duration of the min. switch-on time.
Setting range: 1 to 32,000 seconds
• Lead time (addr. 112,118,124,131,137,143)
Only if there is a threshold value violation for at least
the duration of the lead time is the comparator result
modified.
The lead time can be assigned to times in the range
from 1 to 32,000 seconds.
• Operator (addr. 113,119,125,132,138,144)
Two operators are available for comparing
the measured value and the threshold value.
Operator = 0 means
greater than or equal to (>=)
Operator = 1 means
less than (<)
• Comparator result (addr. 610,611,612,613,614,615)
The result of the comparison between the measured
value and threshold value is in the comparator result.
In this context:
0 = There is no threshold value violation.
1 = There is a threshold value violation.
• Total running time
The sum of all times for which there was a threshold
value violation in the comparator result.
• Combine (addr. 107,126)
Combine the results of Comparators A, B, and C with
the AND/OR operators.
• Total combination result (addr. 616,617)
The combined comparator results of Comparators A,
B, and C are in the total combination result.