110
UMG 96RM-PN
Address
Format
RD/WR
Unit
Comment
Setting range
Default
521
SHORT
RD/WR
-
Switch I/Os of Group 2
0=Output,
1=Input
0,1
0
524
SHORT
RD/WR
-
Inverter Digital output 3
0, 1
*2
0
525
SHORT
RD/WR
-
Inverter Digital output 4
0, 1
*2
0
524
SHORT
RD/WR
-
Inverter Digital output 5
0, 1
*2
0
530
FLOAT
RD/WR
A
Current transformer I4, primary
0 - 1,000,000
(*2)
5
532
FLOAT
RD/WR
A
Current transformer I4, sec.
1.0 - 5.0
5
534
FLOAT
RD/WR
A
Current transformer I5, primary
0.0 - 1,000,000.0
(*2)
1
536
FLOAT
RD/WR
A
Current transformer I5, sec.
1.0 - 5.0
1
538
FLOAT
RD/WR
A
Current transformer I6, primary
0.0 - 1,000,000.0
(*2)
1
540
FLOAT
RD/WR
A
Current transformer I6, sec.
1.0 - 5.0
1
542
SHORT
RD/WR
-
Input type I5
0=Residual current, 1=Temperature
0,1
0
543
SHORT
RD/WR
-
Input type I6
0=Residual current, 1=Temperature
0,1
0
544
FLOAT
RD/WR
-
Temperature offset temp 1
-1000.0 to 1000.0
0
546
FLOAT
RD/WR
-
Temperature offset temp 2
-1000.0 to 1000.0
0
548
SHORT
RD/WR
-
Temperature sensor temp 1
(0=PT100, 1=PT1000, 2=KTY83,
3=KTY84, 4=Resistance in ohms)
0 - 4
0
549
SHORT
RD/WR
-
Temperature sensor temp 2
(0=PT100, 1=PT1000, 2=KTY83,
3=KTY84, 4=Resistance in ohms)
0 - 4
0
550
SHORT
RD/WR
-
Tariff configuration, Input 1
If Input 1 is active, counters
are set in Tariff 1*
0 - 127
0
551
SHORT
RD/WR
-
Tariff configuration, Input 2
If Input 2 is active, counters
are set in Tariff 2*
0 - 127
0
552
SHORT
RD/WR
-
Tariff configuration, Input 3
If Input 3 is active, counters
are set in Tariff 3*
0 - 127
0