Table 1 - Parameter list
0
SHORT
RD/WR
-
Device address
0 - 255
(*1)
1
1
SHORT
RD/WR
kbps
Baud rate (0=9.6kbps, 1=19.2kbps,
0 - 7
4
2=38.4kbps, 3= 57.6kbps
(5 - 7 for internal
4=115.2kbps)
use
only)
3
SHORT
RD/WR
-
Stoppbits
0..3
0
0 = 1 Bit, none parity
1 = 2 Bits, none parity
2 = 1 Bit, even parity
3 = 1 Bit, uneven parity
10
FLOAT
RD/WR
A
Current transformer I1, primary
0 - 1,000,000
(*2)
5
12
FLOAT
RD/WR
A
Current transformer I1, sec.
1 - 5
5
14
FLOAT
RD/WR
V
Voltage transformer V1, prim.
0 - 1,000,000
(*2)
400
16
FLOAT
RD/WR
V
Voltage transformer V1, sec.
100, 400
400
18
FLOAT
RD/WR
A
Current transformer I2, primary
0 - 1,000,000
(*2)
5
20
FLOAT
RD/WR
A
Current transformer I2, sec.
1 - 5
5
Address
Format
RD/WR
Unit
Comment
Setting range
Default
Parameters and Modbus address list
The excerpt of the following parameter list contains settings
necessary for proper operation of the UMG 96RM-PN,
e.g. current transformers and device address. The values
in the parameter list can be described and read.
The excerpt of the measured value list stores
the measured and calculated measured values, status
data for the outputs, and logged values for viewing.
C
A complete overview of the parameters and
measured values as well as explanations
on selected measured values can be found
in the document "Modbus Address List",
which can be found on the CD or online.
C
The addresses listed in this documentation
within the range 0-800 can be set directly
on the device. The addresses in the range
of 1000 and above can only be edited via
Modbus!
(*1) The values 0 and 248 to 255 are reserved and must not be used.
(*2) The adjustable value 0 does not produce any meaningful work values, and must not be used.