103
UMG 96RM-PN
Function parameters
Function
Symbol
Precision class
Measurement range
Display range
Total effective power
P
0.5
5)
(IEC61557-12)
0 to 5.4 kW
0 W to 999 GW *
Total reactive power
QA, Qv
1 (IEC61557-12)
0 to 5.4 kvar
0 varh to 999 Gvar *
Total apparent power
SA, Sv
0.5
5)
(IEC61557-12)
0 to 5.4 kVA
0 VA to 999 GVA *
Total effective energy
Ea
0.5S
5)
6)
(IEC61557-12)
0 to 5.4 kWh
0 Wh to 999 GWh *
Total reactive energy
ErA, ErV
1 (IEC61557-12)
0 to 5.4 kvarh
0 varh to 999 Gvarh *
Total apparent energy
EapA, EapV
0.5
5)
(IEC61557-12)
0 to 5.4 kVAh
0 VAh to 999 GVAh *
Frequency
f
0.05 (IEC61557-12)
45 to 65 Hz
45.00 Hz to 65.00 Hz
Phase current I1 - I3
I
0.2 (IEC61557-12)
0 to 6 Arms
0 A to 999 kA
Measured neutral conductor current I4
IN
1 (IEC61557-12)
0 to 6 Arms
0 A to 999 kA
Residual currents I5, I6
I
Diff
1 (IEC61557-12)
0 to 40 mArms
0 A to 999 kA
Computed neutral conductor current
INc
1.0 (IEC61557-12)
0.03 to 25 A
0.03 A to 999 kA
Voltage
U L-N
0.2 (IEC61557-12)
10 to 300 Vrms
0 V to 999 kV
Voltage
U L-L
0.2 (IEC61557-12)
18 to 520 Vrms
0 V to 999 kV
Power factor
PFA, PFV
0.5 (IEC61557-12)
0.00 to 1.00
0.00 to 1.00
Short-term flicker, long-term flicker
Pst, Plt
-
-
-
Voltage dips (L-N)
Udip
-
-
-
Voltage rises (L-N)
Uswl
-
-
-
Transient overvoltages
Utr
-
-
-
Voltage interruptions
Uint
-
-
-
Voltage unbalance (L-N)
1)
Unba
-
-
-
Voltage unbalance (L-N)
2)
Unb
-
-
-
Voltage harmonics
Uh
Cl. 1 (IEC61000-4-7)
Up to 2.5 kHz
0 V to 999 kV
THD of the voltage
3)
THDu
1.0 (IEC61557-12)
Up to 2.5 kHz
0% to 999%
THD of the voltage
4)
THD-Ru
-
-
-