73
UMG 96RM-PN
The "Response" of the UMG96 RM-PN can appear as
follows:
Name Hex Note
Device address
01
UMG 96RM, address = 1
Function
03
Byte meter
06
Data
00
00hex = 00dez
Data
E6
E6hex = 230dez
Error check (CRC) -
The L1-N voltage read by address 19000 is 230V.
Example: Reading the L1-N voltage
The L1-N voltage is saved in the measured value list
at address 19000. The L1-N voltage is available in
the FLOAT format.
Address = 01 is approved as the UMG 96RM-PN device
address.
The Query Message appears as follows:
Name Hex Note
Device address
01
UMG 96RM, address = 1
Function
03
"Read holding reg."
Start addr. Hi
4A
19000dez = 4A38hex
Start addr. Lo
38
Ind. Value Hi
00
2dez = 0002hex
Ind. Value Lo
02
Error check
-
Summary of Contents for UMG 96 RM-PN
Page 123: ...123 UMG 96RM PN...
Page 128: ...128 UMG 96RM PN...