72
UMG 96RM-PN
RS485 interface
The MODBUS RTU protocol with CRC check on
the RS485 interface can be used to access the data from
the parameter and the measured value lists.
Address range:
1 to 247
Factory default setting:
1
The device address is factory set to 1 and the baud rate
to 115.2 kbps.
Modbus functions (slave)
04 Read input registers
06 Preset single register
16 (10Hex) Preset multiple registers
23 (17Hex) Read/write 4X registers
The sequence of bytes is high before low byte (Motorola
format).
Transmission parameters:
Data bits: 8
Parity: None
Stop bits (UMG 96RM): 2
External stop bits: 1 or 2
Number format: short
16 bit (-2
15
to 2
15
-1)
float
32 bit (IEEE 754)
The message length must not exceed
256 bytes.
C
Broadcast (address 0) is not supported
by the device.
C