Electricity Meters IEC/MID 

Residential 

 

ZCX100Px (Software Version V09.xx.xx)

E450 PLC 1-phase

User Manual

Date: 04.07.2011 
File name: D000029326 E450 ZCX100Px PLC 1ph User Manual en g.docx 
  
© Gyr 

D000029326 en g

Summary of Contents for E450

Page 1: ...icity Meters IEC MID Residential ZCX100Px Software Version V09 xx xx E450 PLC 1 phase User Manual Date 04 07 2011 File name D000029326 E450 ZCX100Px PLC 1ph User Manual en g docx Landis Gyr D000029326...

Page 2: ...rect status inserted and remark about disconnector state added Section 5 1 2 tampering and alarm note added that tempering indications are depending on configuration Adaptation to SW version V01 02 11...

Page 3: ...ent of this user manual is intended for technically qualified person nel of energy supply companies responsible for system planning installa tion and commissioning operation maintenance decommissionin...

Page 4: ...ements ______________________________________________________18 3 4 Dimensions ___________________________________________________________19 3 5 Connections ___________________________________________...

Page 5: ..._________________ 42 5 2 3 5 Test Output LED Mode ____________________________________________ 42 5 2 4 OBIS Codes of Displayed Values________________________________________ 43 5 3 Meter Configuratio...

Page 6: ...pports personal energy management As PLC communication in the low voltage network is free of charge the network is fully available for advanced metering applications Therefore mission critical communi...

Page 7: ...o way communication to metering system with integrated PLC transceiver Wired M Bus interface supports 1 multi energy device gas water district heating Internal disconnector for full disconnection of e...

Page 8: ...cy class 10 20 MID class B IEC class 1 MID class A IEC class 2 Measured quantities A C Active energy bi directional Active and reactive energy Combi System communication P G PLAN GPRS UMTS Built in lo...

Page 9: ...ergy devices The main meter outputs some of which are also inputs are LCD to display measured values and the corresponding OBIS code Optical test output red for active and reactive energy Mechanical o...

Page 10: ...dependent The microprocessor generates pulses for the test diode from the digital value according to the meter constant R Micro processor Test output Phase DFS I U Phase A D A D Digital Multiplier Pu...

Page 11: ...ur quadrant measurement The 5 measurement channels register fixed defined measurement quantities as given in the table below Description OBIS code ME1 Active energy import A QI QIV 1 8 0 ME2 Active en...

Page 12: ...customer premises A manual switch for disconnecting the premises when the customers move away Disconnection if max power has been exceeded over a specified time Bad payers can be either completely di...

Page 13: ...ety information also describes the type and source of the danger its possible consequences and measures for avoiding the danger 2 2 Responsibilities The owner of the meters usually the utility company...

Page 14: ...ately trained personnel are authorised to install the meters Protection earth connection must not be switched with the disconnector Only useful tools have to be used This means a screw driver has to h...

Page 15: ...l port pulse LED disconnector push button and utility sealable reset key The sliding cover has three positions Normal position see Fig 3 1 Service position see Fig 3 2 Read out position see Fig 3 3 In...

Page 16: ...r Fig 3 2 Sliding cover in the service position In the read out position the cover is slid downward so that the optical port and disconnector push button are revealed In this position the cover for th...

Page 17: ...roval number 4 Nominal operating temperature range 5 Auxiliary terminal connection diagram 6 Property plate 7 Auxiliary terminal number inscription 23 24 90 mA solid state relay or optional 5 A latchi...

Page 18: ...onnector A reset key for entering the service menu setting the time and date or manual billing reset located under a sealable cover 3 1 2 Fig 3 5 Control elements 1 Display key 2 Disconnector push but...

Page 19: ...tion 19 54 D000029326 en g E450 PLC 1 phase ZCX100Px User Manual Landis Gyr 3 4 Dimensions Fig 3 6 Meter dimensions 3 5 Connections Fig 3 7 Terminal layout and dimensions The terminals have an opening...

Page 20: ...IC 8A 12V I1 M BUS Fig 3 8 Connection diagram with a 1 pole disconnector an 8 A mechanical relay a 90 mA solid state relay and a wired M Bus optional M 4 3 2 1 L N 23 24 25 26 30 31 28 29 28 29 230V...

Page 21: ...e before using this meter with aluminium conductors The installation site must meet the requirements of the device s protect tion class IP53 and the operating temperature range 40 70 C The E450 is int...

Page 22: ...connection from the mains this must be provided by the end installation Protect disconnector against overcurrent In case the meter has a disconnector this must be protected against over current As th...

Page 23: ...easuring instrument Remove the main fuse and keep it in a safe place until installation is completed 5 Mark the three fixing points on the mounting surface see Fig 4 3 horizontal base of suspension tr...

Page 24: ...onnector screws Terminal Terminal block Fig 4 4 Phase connection terminal 3 Insert the phase and neutral connecting wires in the relevant terminals the terminals are numbered as shown in the connectio...

Page 25: ...res are not squeezed or damaged in the vicinity of the phase connection terminals Connect the respective wires to the S0 input the relay outputs and the M Bus interface if required 1 2 3 4 Fig 4 5 I O...

Page 26: ...tual output creep indicator is displayed 3 Connect a load and check that the output LED starts blinking 4 Check that the meter is measuring correctly Display indicators and their functions are describ...

Page 27: ...3 Once Ser_dAtA is displayed the other menu items can all be obtained by briefly pressing the display key Press the display key until the menu item InStALL is displayed and then press the display key...

Page 28: ...28 54 Installation Landis Gyr D000029326 en g E450 PLC 1 phase ZCX100Px User Manual Fig 4 7 Install menu list 4 6 2 Mains Connection Fig 4 8 Mains menu list...

Page 29: ...direction where x can have the value n for negative energy direction P for positive direction or if there is no cur rent flowing through the phase 4 6 3 PLC Communication 4 6 3 1 PLC Menu The PLC men...

Page 30: ...chronised to the 50 Hz mains and meter is not registered at data concentrator data concentrator unknown unlocked Meter is synchronised to the 50 Hz mains and meter not registered at data concentrator...

Page 31: ...i For a successful installation of an M Bus device the meter must be prop erly pre configured The configuration can be changed with the Landis Gyr MAP110 Service Tool Fig 4 10 shows the process for i...

Page 32: ...ssfully installed it is possible to de install the device from the selected channel by entering the unInSt menu After de installing the InStaLL display is shown again Fig 4 11 shows the process for de...

Page 33: ...data field shows the current mode Inut OFF normal mode i e inversion is off or Inut On inverted mode i e inversion is on The index field shows rELAY 3 Select normal mode Inut OFF or inverted mode Inut...

Page 34: ...off the voltage The display goes off 2 Move the sliding cover to the service position 3 Remove the seals 4 Release and remove the terminal cover 5 Ensure with a phase checker that the phase connecting...

Page 35: ...irection field shows energy flow by quadrants e g if the energy is in the 1st quadrant Q and P arrows are lit As soon as the meter starts with the energy registration active or and reactive the corres...

Page 36: ...s displayed in the value field 0 9 1 indicates that the local time is displayed in the value field The phase voltage presence indication is shown in the segment fields as L1 Depending on the customer...

Page 37: ...splay regardless of which menu or display sequence the key was pressed Reset key Pressing the reset key whilst in operating display will result in billing reset Pressing the reset key whilst the displ...

Page 38: ...menu item The different menu items can be obtained by briefly pressing the display key Fig 5 3 Display menu With the Std_dAtA menu a pre configured list of all important metering data can be shown on...

Page 39: ...for more than 10 seconds the display scrolls through the main values at one second intervals rapid trav erse Exit from the MID data list By holding down the display key for 2 seconds at the end of the...

Page 40: ...the display key scrolls from main value to main value at one second intervals rapid traverse Exit from the service list Hold down the display key at the end of the menu list End position until the men...

Page 41: ...ect time and date to prevent incorrect time data in the meter This should be performed either by using Landis Gyr MAP110 Service Tool during the set up of the metering system or manually via keys show...

Page 42: ...efly to move to the next value By double clicking the display button or after timeout the test mode is disabled and the operating display is shown Fig 5 5 Switching the test mode on off If one of the...

Page 43: ...cksum of metering code 0 2 8 Active energy A import total 1 8 0 Active energy A export total 2 8 0 Reactive energy R total 3 8 0 Reactive energy R total 4 8 0 Reactive energy Ri quadrant I total 5 8 0...

Page 44: ...operating status C 5 0 Number of power failures in all phases C 7 0 Number of long power failures in any phase C 7 9 Number of power failures in any phase C 7 21 Operating time C 8 0 Operating time r...

Page 45: ...on the disconnector can be controlled remotely locally or manually The mode is defined within the meter configuration Details on the operat ing modes are described in the E450 functional description D...

Page 46: ...egory depending on severity Critical errors Communication errors Other errors Critical errors indicate severe problems but the device can still operate However the data measured and stored in the mete...

Page 47: ...p in four groups of two digits Each digit of the error code represents four errors i e four bits of the error register The status of the four bits is shown in hexadecimal code i e the single digits ma...

Page 48: ...th the next read write to the profiles or reset via communication F F 00 00 00 10 Disconnector Control Unit Failure Error Purpose Indicates a possible failure of the disconnector control unit Category...

Page 49: ...start up sequence Category Critical error Reset The error is not reset automatically the register must be cleared via communication Event Error register cleared is triggered If repeated the meter mus...

Page 50: ...imes result in higher measuring deviations Therefore it is recommended to use long measuring times to obtain the desired accuracy The following tables show the minimal test times needed to achieve the...

Page 51: ...ectronic waste treatment process The waste treatment company must be accepted by the officials End processing of the product and recycling of its components must always be carried out in accordance wi...