Figure 3-69
Removing the bottom cable covers and drilling holes
(1) Power cable covers
(2) Signal cable hole
Step 3
Remove the rear cover from the bypass cabinet.
You are advised to remove the side panel from the bypass cabinet before connecting cables.
Step 4
Remove the copper bars between the mains and bypass input wiring terminals, as shown in
. (Perform this step only when the mains input and bypass input use different
power sources.)
Properly keep the removed copper bars and bolts.
(Optional) If copper bar protective covers are installed for the bypass cabinet, remove the protective
covers and then the connecting copper bars. The protective covers need to be reinstalled after the
connecting copper bars are removed.
shows how to remove the protective covers.
Step 5
Connect a ground cable to the UPS.
If you do not ground the UPS as required, electromagnetic interference, electric shocks, or fire
may occur.