UPS5000-E-(350 kVA-800 kVA)
User Manual (50 kVA Power Modules)
3 Installation
Issue 05 (2018-01-08)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
56
Item
350 kVA
400 kVA
450 kVA
500 kVA
550 kVA
PE
185
240
240
240
240
Bypa
ss
input
conn
ector
Bypass input
current (A)
532
608
684
760
836
Recomme
nded
cross-secti
onal area
(mm
2
)
L1
2 x (4 x 185)
2 x (4 x 240)
3 x (4 x 185)
3 x (4 x 185)
3 x (4 x 240)
L2
L3
N
PE
185
240
240
240
240
Outp
ut
conn
ector
Output current (A)
532
608
684
760
836
Recomme
nded
cross-secti
onal area
(mm
2
)
U
2 x (4 x 185)
2 x (4 x 240)
3 x (4 x 185)
3 x (4 x 185)
3 x (4 x 240)
V
W
N
PE
185
240
240
240
240
Batte
ry
input
conn
ector
Nominal discharge
current (A)
768
877
987
1096
1206
Maximum
discharge current
(A)
919
1051
1182
1313
1444
Recomme
nded
cross-secti
onal area
(mm
2
)
+
2 x (3 x 185)
2 x (3 x 240)
3 x (3 x 150)
3 x (3 x 185)
3 x (3 x 240)
N
-
PE
185
240
240
240
240
Table 3-3
Recommended cross-sectional areas for power cables (600 kVA–800 kVA)
Item
600 kVA
650 kVA
700 kVA
750 kVA
800 kVA
Main
s
input
conn
ector
Mains input current
(A)
1066
1155
1244
1333
1422
Recomme
nded
cross-secti
onal area
(mm
2
)
L1
4 x (4 x 185)
4 x (4 x 240)
4 x (4 x 240)
4 x (4 x 240)
4 x (4 x 240)
L2
L3
N