UPS5000-E-(350 kVA-800 kVA)
User Manual (50 kVA Power Modules)
3 Installation
Issue 05 (2018-01-08)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
83
Figure 3-32
Installing an expansion bolt (unit: mm)
1.
Drill holes in the ground by using a hammer drill. The hole depth is 52 mm to 60 mm.
2.
Partially tighten the expansion bolt and vertically insert it into the hole. Knock the
expansion bolt using a rubber mallet until the expansion sleeve is fully inserted into the
hole.
3.
Partially tighten the expansion bolt.
4.
Remove the bolt, spring washer, and flat washer.
----End
Combining Power Cabinets and Bypass Cabinets
The power cabinets and bypass cabinets are separately packed for delivery. Before installing
the UPS, combine the power cabinets and bypass cabinets. Before combining the cabinets,
ensure that the required fittings are complete.
Table 3-9
Fitting list
Mounting
Fitting
Number of
Fittings
Screw
Specifications
Number of
Bolts (PCS)
Torque
(N·m)
Remarks
Bottom
connecting
plate
2
M12x25
8
47
Fittings are delivered
with the UPS. You can
see the fittings after
unpacking the bypass
cabinet.
The two soft copper bars
are numbered 52.
If holes are drilled for
routing cables at the top
of the cabinet, attach
grommet strips on the
hole edges to protect
Top
connecting
plate
2
M6x30
8
3
Soft
connecting
copper bar
2
M12x45
10
47
Grommet
N/A
N/A
N/A
N/A