UPS5000-E-(350 kVA-800 kVA)
User Manual (50 kVA Power Modules)
5 Operations
Issue 05 (2018-01-08)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
248
Figure 5-11
Inv. OFF screen
To shut down the inverter on the
Maintenance
screen, tap
System Info
>
Maintenance
.
On the WebUI
a.
In the browser, enter the UPS IP address in the address box.
b.
On the login page, select a display language, enter a
User name
and
Password
, and
click
Login
.
c.
On the homepage, choose
Monitoring
>
Control
, and click
Inv. OFF
. In the
displayed dialog box, click
OK
to shut down the inverter.
Figure 5-12
Shutting down the inverter
After the inverter shuts down, the UPS works in bypass mode if the bypass is
normal, as shown in
; the UPS supplies no power and the loads power
off if the bypass is abnormal, as shown in