UPS5000-E-(350 kVA-800 kVA)
User Manual (50 kVA Power Modules)
3 Installation
Issue 05 (2018-01-08)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
68
Table 3-6
Specifications and number of screws (400 kVA or 500 kVA UPS)
Position
Screw Specification
Quantity (PCS)
Soft copper bar
M12x35
26
Battery copper bar
component
M8x20
4
Top connecting plate
M6x30
8
Middle connecting plate
M6x30
8
Bottom connecting plate
M12x35
8
Table 3-7
Specifications and number of screws (600 kVA UPS)
Position
Screw Specification
Quantity (PCS)
Soft copper bar
M12x45 screw assembly
26
Battery copper bar
component
M6x30 screw assembly
4
Top connecting plate
M6x20 screw assembly
8
Middle connecting plate
M6x20 screw assembly
8
Bottom connecting plate
M12x35 screw assembly
8
Procedure
Step 1
Open the front door of the bypass cabinet and remove the covers of the power distribution
subrack.
The covers of the power distribution subrack can be removed from the bypass cabinet only when all
switches are OFF.