UPS5000-E-(350 kVA-800 kVA)
User Manual (50 kVA Power Modules)
4 User Interface
Issue 05 (2018-01-08)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
176
Item
Description
Battery
capacity
(Ah)
The value range is 5 Ah to 9999 Ah. 600 Ah is set by default for the 400 kVA,
500 kVA, and 600 kVA UPSs, and 800 Ah is set by default for the 800 kVA
UPS.
Number
of cells
Each 12 V battery consists of six cells. The value range is 180 to 276. The
default value is 240.
A cell consists of electrodes and electrolytes, which is the basic unit for the battery. Each cell has a
nominal voltage of 2 V. A battery is a module consisting of single or multiple cells in a shell. Each
battery has a nominal voltage of 2 V or 12 V. The number of cells must be a multiple of 12 (for
example, 180 and 192).
Cell float voltage
,
Cell equalized volt
,
Float volt. temp. comp. coef.
, and
EOD voltage threshold
are set for cells.
Advanced Parameters
Set
System capacity
and
Power module capacity
according to site specifications. Incorrect
settings may generate an overload alarm, which affects normal UPS running.
Figure 4-33
Advanced Param. screen 1
Item
Description
System
capacity
(kVA)
The rated system capacity equals the capacity of each power module
multiplied by the number of requisite power modules. If this is set
incorrectly, the
Module quantity mismatch
alarm will be generated.
Power
module
Rated power module capacity.