UPS5000-E-(350 kVA-800 kVA)
User Manual (50 kVA Power Modules)
4 User Interface
Issue 05 (2018-01-08)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
174
Item
Description
frame format that the upstream device Modbus supports. The value can be
set to 1 or 2. The default value is
1
.
Batt. temp.
sensors
A maximum of four battery temperature sensors can be cascaded. The
default value is
0
.
Start addr.
of batt.
temp.
sensor
Set this parameter by using the DIP switch on the battery temperature
sensor. The address range is 16–28. Ensure that the address set on the LCD
is the same as that set for the DIP switch. Otherwise, communication fails.
BMUs
A maximum of 12 BMUs can be cascaded. The default value is
0
.
Figure 4-31
Communication screen 3
Item
Description
BMU start
address
Use the DIP switch on the BMU to set the BMU start address to 112.
Ensure that the address set on the LCD is the same as that set for the DIP
switch. Otherwise, communication cannot be implemented.
Amb. temp
& humid
sensors
/
Start
addr. of
amb. temp.
& hum.
sensors
An ambient temperature and humidity sensor has the same appearance as a
battery temperature sensor. The two types of sensors can be cascaded (up
to four). The ambient temperature and humidity sensor address range is
32–44, which is different from the battery temperature sensor. Therefore,
you can use the sensor as an ambient temperature and humidity sensor or
battery temperature sensor by setting the address.
NTC
The short-distance battery temperature sensor monitors the ambient
temperature near batteries, and ensures that batteries work reliably and
securely. The default status is
Disable
. If a short-distance battery
temperature sensor is configured, set
NTC
to
Enable
.
WiFi SSID
When using the mobile app for site setup or inspection, set WiFi SSID
after connecting a WiFi module over a USB port to identify the WiFi