UPS5000-E-(350 kVA-800 kVA)
User Manual (50 kVA Power Modules)
8 Technical Specifications
Issue 05 (2018-01-08)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
282
Item
400 kVA
500 kVA
600 kVA
800 kVA
±0.05%).
Total harmonic
distortion of output
voltage (THDv)
≤ 1% (full linear load)
≤ 4% (full non-linear load)
Output PF
1
Transfer time
0 ms (uninterruptible transfer)
≤ 20 ms (interruptible transfer)
Output voltage
unbalance
Voltage unbalance: ±3%; phase unbalance: ±2°
Overload capability
Inverter overload capability:
100% < load ≤ 110%: transfer to bypass mode after 60 minutes
110% < load ≤ 125%: transfer to bypass mode after 10 min
125% < load ≤ 150%: transfer to bypass mode after 1 min
Load > 150%: transfer to bypass mode after 200 ms
8.9 System Electrical Specifications
Item
400 kVA
500 kVA
600 kVA
800 kVA
Redundancy
design
The auxiliary power supplies, centralized controllers, and parallel signals
use redundancy design.
ECO
Supported