UPS5000-E-(350 kVA-800 kVA)
User Manual (50 kVA Power Modules)
3 Installation
Issue 05 (2018-01-08)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
57
Item
600 kVA
650 kVA
700 kVA
750 kVA
800 kVA
PE
240
240
240
240
240
Bypa
ss
input
conn
ector
Bypass input
current (A)
912
988
1064
1140
1215
Recomme
nded
cross-secti
onal area
(mm
2
)
L1
4 x (4 x 185)
4 x (4 x 240)
4 x (4 x 240)
4 x (4 x 240)
4 x (4 x 240)
L2
L3
N
PE
240
240
240
240
240
Outp
ut
conn
ector
Output current (A)
912
988
1064
1140
1215
Recomme
nded
cross-secti
onal area
(mm
2
)
U
4 x (4 x 185)
4 x (4 x 240)
4 x (4 x 240)
4 x (4 x 240)
4 x (4 x 240)
V
W
N
PE
240
240
240
240
240
Batte
ry
input
conn
ector
Nominal discharge
current (A)
1316
1425
1535
1645
1754
Maximum
discharge current
(A)
1576
1707
1838
1970
2101
Recomme
nded
cross-secti
onal area
(mm
2
)
+
3 x (3 x 240)
4 x (3 x 185)
4 x (3 x 240)
4 x (3 x 240)
4 x (3 x 240)
N
-
PE
240
240
240
240
240
When selecting, connecting, and routing power cables, follow local safety regulations
and rules.
If external conditions such as cable layout or ambient temperatures change, perform
verification in accordance with the IEC-60364-5-52 or local regulations.
If the rated voltage is 400 V, multiply the currents by 0.95. If the rated voltage is 415 V,
multiply the currents by 0.92.
If primary loads are non-linear loads, increase the cross-sectional areas of neutral wires
1.5–1.7 times.
The nominal battery discharge current refers to the current of forty 12 V batteries at 480
V in standard configuration.
The maximum battery discharge current refers to the current when forty 12 V batteries in
standard configuration, that is, two hundred and forty 2 V battery cells (1.67 V/cell), stop
discharging.