After the inverter starts, the UPS still works in bypass mode and the inverter is on standby.
shows the power flow displayed on the
System Status
screen. If the bypass is not
normal, the inverter supplies power immediately. If the inverter is not started, the UPS may be
disconnected.
Figure 5-17
System Status screen
----End
5.6 Testing Batteries
5.6.1 Forced Equalized Charging Test
Context
Before a forced equalized charging test, ensure that: