UPS5000-E-(350 kVA-800 kVA)
User Manual (50 kVA Power Modules)
8 Technical Specifications
Issue 05 (2018-01-08)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
279
UPS
Maintenance
bypass switch
Mains input
switch
Bypass input
switch
Output
switch
UPS5000-E-50
0K-FM
1000 V AC/800
A/3P
1000 V
AC/1000 A/3P
1000 V AC/800
A/3P
1000 V AC/800
A/3P
UPS5000-E-60
0K-SM
1000 V
AC/1000 A/3P
-
-
-
UPS5000-E-60
0K-FM
1000 V
AC/1000 A/3P
1000 V
AC/1250 A/3P
1000 V
AC/1000 A/3P
1000 V
AC/1000 A/3P
UPS5000-E-80
0K-SM
1000 V
AC/1250 A/3P
-
-
-
UPS5000-E-80
0K-FM
1000 V
AC/1250 A/3P
1000 V
AC/1600 A/3P
1000 V
AC/1250 A/3P
1000 V
AC/1250 A/3P
8.3 Environment Parameters
Environment
Feature
400 kVA
500 kVA
600 kVA
800 kVA
Operating
temperature
0–40°C
Storage
temperature
–40°C to +70°C
Relative
humidity
0%–95% RH (non-condensing)
Altitude
0–1000 m
When the altitude is greater than 1000 m and less than 4000 m, the rated
power should be derated. For details, see the IEC62040-3.
8.4 Safety Regulations and EMC
Safety and
EMC
400 kVA
500 kVA
600 kVA
800 kVA
Safety
regulations
EN62040-1: 2013
IEC62040-1: 2013
YD/T2165-2010
EMC
EN62040-2
IEC62040-2