UPS5000-E-(350 kVA-800 kVA)
User Manual (50 kVA Power Modules)
3 Installation
Issue 05 (2018-01-08)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
96
Step 2
Drill holes for installing expansion bolts, and install expansion sleeve.
Step 3
Open the front door of the cabinet and remove the support baffle plates from the front of the
cabinet. The methods of removing baffle plates for different UPS models are the same.
shows how to remove support baffle plates for a 600 kVA UPS. Remove the rear cover.
Figure 3-46
Removing support baffle plates
Step 4
Secure the antiseismic kits to the front and back of the cabinet using M6 screws. The
tightening torque is 3 N·m. The installation methods for different UPS models are the same.
shows how to install antiseismic kits for a 600 kVA UPS.
Figure 3-47
Securing the antiseismic kits to the cabinet
Step 5
Adjust the cabinet to ensure that the expansion bolt holes align with the half holes below.
Step 6
Use expansion bolts to firmly lock the front and rear antiseismic kits to the ground. The
installation methods for different UPS models are the same.
antiseismic kits for a 600 kVA UPS.