UPS5000-E-(350 kVA-800 kVA)
User Manual (50 kVA Power Modules)
C Alarm List
Issue 05 (2018-01-08)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
315
Alarm
ID
(Alarm
ID-Caus
e ID)
Alarm
Name
Severit
y
Cause
Solution
excessive.
The
configure
d number
of
redundant
modules
is
incorrect.
of redundant modules.
0096-1
ECO volt.
Abnormal
Minor
The ECO
bypass
voltage or
frequency
is out of
the preset
range.
The ECO
bypass
voltage or
frequency
range is
incorrectl
y set.
The
bypass
input
sequence
is reverse
or the
neutral
wire is
disconnec
ted.
1.
Check the bypass input voltage
and frequency.
2.
Check that the rated voltage,
rated frequency, ECO bypass
voltage range, and frequency
range are correctly set.
3.
Check that the bypass cables
and circuit breakers are
correctly connected.
0098-1
Bypass
current not
shared
Minor
The
output
and input
circuit
breakers
are OFF.
The
length of
the bypass
input or
output
cables is
incorrect.
1.
Check that the output and
bypass input circuit breakers on
each rack are ON.
2.
Check that bypass input and
output power cables on each
rack meet the length
requirements.
3.
Rectify any bypass SCR
open-circuit.