5 Operations
Issue 05 (2018-01-08)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
264
Figure 5-34
Clearing faults
Step 3
Check that the EPO alarm is cleared by viewing active alarms. If the system bypass input is
normal, the UPS transfers to bypass mode.
Viewing active alarms on the LCD
Choose
System Info
>
Alarms
and tap
Active Alarms
to check that the EPO alarm is
cleared.
Viewing active alarms on the WebUI
Choose
Monitoring
>
Active Alarms
to check that the EPO alarm is cleared.
Step 4
Start the inverter.
----End
5.11 Exporting Data
Prerequisites
You have logged in to the WebUI.
Context
The following data can be exported:
Historical alarms
Logs
E-Label
CIM version
Fault Data
This topic describes how to export historical alarms.
Procedure
Step 1
Choose
Query
>
Historical Alarms
, and set
Severity
,
Generated
, and
Cleared
.