UPS5000-E-(350 kVA-800 kVA)
User Manual (50 kVA Power Modules)
5 Operations
Issue 05 (2018-01-08)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
267
Figure 5-38
Confirmation message
Step 4
Check that the load power is stable (that is, no transient surge results in overload, which may
cause the UPS to transfer to bypass mode), and tap
Yes
.
Step 5
Set
Module cycle hiber. period (d)
to an integer ranging from
1
to
100
. The default value is
30
.
----End
5.12.2 WebUI
Procedure
Step 1
On the login page, enter a user name and password, and click
Login
.
Step 2
Choose
Monitoring
>
Param. Settings
>
Advanced Param.
, as shown in
Figure 5-39
Hibernation parameters on the WebUI