5 Commissioning the Cooling System
Issue 06 (2020-03-20)
Copyright © Huawei Technologies Co., Ltd.
37
Parameter
Description
Configuration
Principle
Default
Value
disabled, this device is
operating according to its
own control. If the
teamwork function is
enabled, this device
works in harmony with
others that in the same
group.
distribution.
Networking
mode
Networking mode for the
teamwork. The
networking mode set on
the screen must be
consistent with the actual
networking mode.
Otherwise, the teamwork
control function will be
unavailable. If the
networking mode
changes, select the
corresponding
networking mode on the
screen. If the networking
mode is changed on the
screen, the software will
restart and then run in the
new networking mode.
(For V200R002 version,
the software will not
restart when the
networking mode is
changed )
Networked over CAN or
MAC_CAN.
CAN
network
indicates
teamwork control over a
CAN bus,
MAC_CAN
network
teamwork control
over an FE port.
MAC_CAN
network
Number of
smart cooling
products in this
group
Number of the smart
cooling products in this
group (1 to 32 can be
set).
Total number of the smart
cooling products in this
group.
3
Number of
running smart
cooling
products in this
group
Number of active units in
a group. The value ranges
from 1 to
Number of
smart cooling products
in this group
.
The host allocates running
units by smart cooling
product unit address in
ascending order, which is
from 1 to 32. The rest will
become the standby ones.
2
Rotation
function
Disable or enable the
active and standby smart
cooling products to
change identity after a
certain time, maximizing
their service life.
This function is
recommended when the
heat is even.
Disable
Rotation
Rotation days (1–30).
7 by default
7 day (s)