FusionModule5000 Smart Modular Data Center
Commissioning Guide
7 FAQ
Issue 06 (2020-03-20)
Copyright © Huawei Technologies Co., Ltd.
117
Step 7
Click
Select
in the
Output Dry Contact
column corresponding to
Operation log full
as
required, select
Yes
or
No
for DO1 or DO2, and click
OK
.
Select a DO not used by other functions. Otherwise, the association setting fails.
Step 8
Click
Select
in the
Loudspeaker
column corresponding to
Operation log full
as required, set
Loudspeaker
to
Yes
or
No
, and click
OK
.
----End
7.1.11 How Is a Signal Name Changed
Context
In this example, the smoke sensor is connected to the AI/DI_3 port on the ECC800.
The following procedure describes how to change the signal name of AI/DI_3. Other
signal names can be changed in a similar way.
Procedure
Step 1
Log in to the ECC800 WebUI as an administrator.
Step 2
Choose
System Settings
>
Signal Name Modify
. The
Batch Signal Configuration
page is
displayed.
Step 3
Set
Device type
to
ECC800
, set
Device name
to
ECC800
, and click
OK
.
Step 4
On the query result tab page, set the new signal name of
AI/DI_3
to
Smoke
and click
Submit
.
Step 5
Choose
Monitoring
>
System
>
ECC800
>
Running Parameters
>
AI/DI_3 Port Settings
.
Check that the signal name of AI/DI_3 has been changed to
Smoke
.
----End
7.1.12 How Should I Link the Smoke Alarm with the Alarm
Beacon over the ECC800 WebUI
Prerequisites
The alarm beacon is connected to the DO port on the ECC800.
Context
This section describes how to set an alarm linkage by linking output dry contact of the smoke
alarm on the multi-functional sensor to the DO2 port.
After the smoke alarm is linked with the alarm beacon, if smoke is detected inside the smart
module, the alarm beacon connecting to the corresponding DO2 port will generate an audible
and visual alarm.