6 Commissioning the Management System
Issue 06 (2020-03-20)
Copyright © Huawei Technologies Co., Ltd.
98
2N non-isolation scenario: The system has only one power distribution cabinet and is
working in dual-power supply mode.
2N isolation scenario: The system has two power distribution cabinets and is working in
single-power supply mode.
For details about the power distribution solution, refer to the power distribution wiring diagram supplied
with the product.
Step 3
Double-click a network cabinet to access the
Basic Configuration
page.
Step 4
Check whether the branch information in
Apply Power Distribution Standard
Configuration
is consistent with the actual situation, and set electricity configuration
parameters such as
Device Name
,
Cabinet height
,
Power system
,
Number of power
supplies
, and
Rated cabinet power
as required.
The settings in the following table are used as examples to describe the basic configuration.
Table 6-28
Basic configuration
Parameter
Setting
Description
Device Name
IT Cabinet 101
Set based on the actual device
name.
Cabinet height
42
U space quantity of the cabinet.
Power
Distribution
Parameter
Settings
Power
system
Single-phase
Set single-phase or three-phase
based on the actual power supply.
Number
of power
supplies
2
rPDU quantity.
Rated
cabinet
power
6.00
Set based on the actual rated
power of the cabinet.
rPDU-A01
PDU80001
>
1QF1(L1)
Select a power distribution device
and power distribution branch for
the rPDU numbered rPDU-A01 in
the cabinet.
rPDU-B01
PDU80001
>
2QF1(L1)
Select a power distribution device
and power distribution branch for
the rPDU numbered rPDU-B01 in
the cabinet.
Branch auto-fill mode
Ascending order
Descending order
If the branch for the first
cabinet is
1QF1(L1)
,
2QF1(L1)
, the branches for
subsequent cabinets are
1QF2(L2)
,
2QF2(L2)
, and the
like.
If the branch for the first
cabinet is
1QF10(L1)
,