FusionModule5000 Smart Modular Data Center
Commissioning Guide
5 Commissioning the Cooling System
Issue 06 (2020-03-20)
Copyright © Huawei Technologies Co., Ltd.
33
Parameter
Description
Configuration Principle
the temperature is to be
controlled based on the
minimum data value collected
by the collector.
Control point
temperature
setpoint
After the Temperature and humidity
control type and the temperature
value under this type are set, the
device conducts cooling or heating
based on the settings.
Set this parameter as required.
Return air temperature: 26–35°C
recommended
Supply air temperature:
18–24°C recommended
Cold aisle temperature: 18–24°C
recommended
Hot aisle temperature: 26–35°C
recommended
Control point
humidity
setpoint
After the Temperature and humidity
control type and the humidity value
under this type are set, the device
conducts humidifying or
dehumidifying based on the
settings.
Set this parameter as
required.40%–60% RH
recommended
Step 4
Go back to home screen, and tap
Running
>
Device Details
>
T/H sensor
to check that the
cold aisle temperature and humidity are displayed and the values are reasonable.