FusionModule5000 Smart Modular Data Center
Commissioning Guide
6 Commissioning the Management System
Issue 06 (2020-03-20)
Copyright © Huawei Technologies Co., Ltd.
51
6
Commissioning the Management System
6.1 Preparations and WebUI Login
Prerequisites
The operating system of Windows 7 or later is supported.
It is recommended that the screen resolution be 1366 x 768 or higher.
Browser: IE9 and later versions; Firefox and later versions; Chrome and later versions
Procedure
Step 1
Connect a network cable between the PC network port and the WAN_1 port (protected by a
security mechanism) on the ECC800.
Table 6-1
Default IP addresses for the WAN and LAN ports on the ECC800
Port
Default IP Address
WAN_1
192.168.1.10
WAN_2
192.168.0.10
LAN_1 and LAN_2
192.168.248.10
The WAN_1 port IP address cannot be set to an IP address in any of the following network
segments: 192.168.0.x, 192.168.8.x, 192.168.248.x, and 192.168.245.x.
IP addresses for the WAN_1 and WAN_2 ports should not be set in the same network
segment.
In some customized scenarios, the default IP address for the WAN_2 port is
192.168.248.10. The default value prevails.
WAN ports support the Internet access and LAN ports support the intranet access. Connect
the PC network port to the WAN port or LAN port on the ECC800 based on the access
network.
Step 2
Configure the PC IP address and the WAN_1 IP address in the same network segment.