FusionModule5000 Smart Modular Data Center
Commissioning Guide
7 FAQ
Issue 06 (2020-03-20)
Copyright © Huawei Technologies Co., Ltd.
110
Path
Parameter
Name
Setting
and click
Add
Device
. The
parameters for
adding devices
are displayed.
Connect To
Select
ECC800
from the drop-down list box.
Communicatio
ns Port
Select
COM3
from the drop-down list box.
NOTE
The setting example indicates that the T/H sensor is
connected to the COM3 port on the ECC800. If the T/H
sensor is connected to another port, enter the number of the
connected port.
Device
Address
In this example,
Device Address
is set to
1
. During
actual configuration, set the device address for the
T/H sensor based on the actual situation.
3.
Click
Test Connect
to check whether the T/H sensor connects to the ECC800 properly.
−
If the T/H sensor connects to the ECC800 properly, click
Confirm
. The connected
devices are displayed in the
Number of connected devices
list.
−
If the T/H sensor does not connect to the ECC800 properly, check whether the cable
between the T/H sensor and the ECC800 is connected properly, whether the T/H
sensor and ECC800 are running properly, and whether the input parameters are
consistent with the T/H sensor parameters.
Step 3
Check functions of the T/H sensor.
Table 7-7
Function check
Check Method
Normal Connection Status
Check the running information
about the T/H sensor on the
WebUI.
Choose
Monitoring
>
Aisle
>
T/H Sensor Group
>
T/H Sensor n
>
Running Info
, and check the current
T/H information of the cabinet.
Set T/H sensor alarm thresholds.
Choose
Monitoring
>
Aisle
>
T/H Sensor Group
>
T/H Sensor n
>
Running Parameters
, and set
High
temperature alarm threshold
,
Low temperature
alarm threshold
,
High humidity alarm threshold
,
and
Low humidity alarm threshold
as required.
NOTE
The default values of
High temperature alarm threshold
,
Low temperature alarm threshold
,
High humidity alarm
threshold
, and
Low humidity alarm threshold
are
30.0°C
,
5.0°C
,
85.0% RH
, and
15.0% RH
, respectively.
----End
7.1.6 How to Set and Add the T/H Sensor (BOM Number:
02310NBS)
If a T/H sensor is installed, perform the following steps to configure it.