FusionModule5000 Smart Modular Data Center
Commissioning Guide
5 Commissioning the Cooling System
Issue 06 (2020-03-20)
Copyright © Huawei Technologies Co., Ltd.
48
Figure 5-16
Selecting commissioning items
If the system is not configured with the humidifier components, the humidifier commissioning items
will not appear on the screen.
If the humidification function are disabled, you cannot select the humidifier item.
All the items are selected by default if you first enter the screen where you select commissioning
items. Except that the indoor fan item is mandatory, you can clear other commissioning items that
are not required.
Step 5
Tap
Yes
. The component startup commissioning screen is displayed, as shown in
Figure 5-17
Fan commissioning
The fan commissioning item is mandatory. After commissioning for a component succeeds, the system
automatically performs commissioning for the next component you selected. If commissioning fails,
startup wizard ends.
Step 6
View the commissioning result.