FusionModule5000 Smart Modular Data Center
Commissioning Guide
5 Commissioning the Cooling System
Issue 06 (2020-03-20)
Copyright © Huawei Technologies Co., Ltd.
30
Menu
Parameter
Description
Configuration
Principle
value collected by the
collector.
Temperature setpoint
After the
Temperature and
humidity control
type and the
temperature value
under this type are
set, the device
conducts cooling
or heating based
on the settings.
Set this parameter as
required.
Return air
temperature: 26–35°C
recommended
Supply air
temperature: 18–24°C
recommended
Cold aisle
temperature: 18–24°C
recommended
Hot aisle temperature:
26–35°C
recommended
Humidity setpoint
After the
Temperature and
humidity control
type and the
humidity value
under this type are
set, the device
conducts
humidifying or
dehumidifying
based on the
settings.
Set this parameter as
required.
40%–60% RH
recommended
Cold aisle sensor 1
Cold aisle sensor 2
Cold aisle sensor 3
Cold aisle sensor 4
Cold aisle sensor 5
The sensors in
cold aisles can be
set to
Enable
or
Disable
.
The cold aisle sensors
outside the cabinet need
to be enabled when they
are installed.
Hot aisle sensor 1
Hot aisle sensor 2
Hot aisle sensor 3
Hot aisle sensor 4
Hot aisle sensor 5
The sensors in hot
aisles can be set to
Enable
or
Disable
.
The hot aisle sensors
outside the cabinet need
to be enabled when they
are installed.
Comm Settings
(visible for
V200R002
version)
Modbus Comm
address
Set the
communication
address of the
smart cooling
product as
planned. The
EMS
The communication
addresses of two smart
cooling products
connecting to the same
EMS must be unique.