FusionModule5000 Smart Modular Data Center
Commissioning Guide
5 Commissioning the Cooling System
Issue 06 (2020-03-20)
Copyright © Huawei Technologies Co., Ltd.
29
Menu
Parameter
Description
Configuration
Principle
that the dehumidification
function will be enabled
when the main power is
active and the ambient
humidity exceeds the
certain humidity range of
the humidity set point.
T/H sensor
(visible for
V200R002
version)
Temperature and
humidity control type
Cold aisle
,
Hot
aisle
,
Return air
,
or
Supply air
can
be set as required.
The temperature
and humidity set
points correspond
to the selected
control type can
be set.
When the application
scenario is cold or hot
aisle containment,
you are advised to
choose
Cold aisle
if
the cold aisle T/H
sensors are
configured, and
choose
Supply air
if
the cold aisle T/H
sensors are not
configured.
When the application
scenario is non-aisle
containment, you are
advised to choose
Return air
, and
choose
Cold aisle
if
the cold aisle T/H
sensors are
configured.
Hot aisle
is not
recommended.
Temperature control
mode
This parameter
controls the
temperature inside
the room or aisles
based on the
Average value
,
Max value
, or
Min value
of the
temperatures
collected by each
sensor.
Average value: Select
Average value
if the
temperature is to be
controlled based on
the averaged data
value collected by the
collector.
Max value: Select
Max value
if the
temperature is to be
controlled based on
the maximum data
value collected by the
collector.
Min value: Select
Min value
if the
temperature is to be
controlled based on
the minimum data