FusionModule5000 Smart Modular Data Center
Commissioning Guide
6 Commissioning the Management System
Issue 06 (2020-03-20)
Copyright © Huawei Technologies Co., Ltd.
61
Path
Parameter
Name
Default
Value
Setting
System CT ratio
to
250
.
If
Rated system
current
is 160 A, set
System CT ratio
to
200
.
2.
Set the parameters for other general input units in the same way or by synchronizing
parameters.
Path:
Maintenance
>
Parameter Sync
Step 2
Set parameters for power distribution units on the ECC800 WebUI.
1.
(Optional) To modify the branch signal name of the power distribution unit, choose
System Settings
>
Signal Name Modify
and access the
Batch Signal Configuration
to
modify the name, and then tap
Submit
.
2.
The following is an example of how to display two branches for power distribution unit
1.
Choose
Monitoring
>
Power Distribution
>
Power Distribution Unit 1
>
Display
Configuration
, select
Running Information Display
and
Running Parameters
Display
corresponding to QF1 and QF2, and then tap
Submit
.
3.
Configure the power distribution settings for power distribution unit 1.
Table 6-4
Power distribution settings for a power distribution unit
Path
Parameter Name
Default
Value
Description
Monitoring
>
Power
Distribution
>
Power
Distribution
Unit 1
>
Running
Parameters
>
Power
Distribution
Settings
QF1 Rated current (QF1)
QF2 Rated current (QF2)
32
Rated current 32 A for
each branch.
QF1 Branch circuit breaker in
use (QF1)
QF2 Branch circuit breaker in
use (QF2)
Enable
When the parameter is
set to
Disable
for a
branch, all alarms of the
branch will not be
reported.
When the parameter is
set to
Enable
for a
branch, all alarms of the
branch will be reported.
4.
Set the parameters for other power distribution units in the same way or by
synchronizing parameters.
Choose
Maintenance
>
Parameter Sync
.
----End