background image

FusionCol8000-E240 Modular Indirect Evaporative

Cooling System

User Manual

Issue

02

Date

2021-04-15

HUAWEI TECHNOLOGIES CO., LTD.

Summary of Contents for FusionCol8000-E240

Page 1: ...FusionCol8000 E240 Modular Indirect Evaporative Cooling System User Manual Issue 02 Date 2021 04 15 HUAWEI TECHNOLOGIES CO LTD ...

Page 2: ...cribed in this document may not be within the purchase scope or the usage scope Unless otherwise specified in the contract all statements information and recommendations in this document are provided AS IS without warranties guarantees or representations of any kind either express or implied The information in this document is subject to change without notice Every effort has been made in the prep...

Page 3: ...tion engineers Maintenance engineers Symbol Conventions The symbols that may be found in this document are defined as follows Symbol Description Indicates a hazard with a high level of risk which if not avoided will result in death or serious injury Indicates a hazard with a medium level of risk which if not avoided could result in death or serious injury Indicates a hazard with a low level of ris...

Page 4: ...1 04 15 Building scenario Added the floor drain pipe Building scenario Changed the positions of water refill and drain pipe ports Optimized the content related to water seals Building scenario Updated 3 7 Optional Installing Motorized Dampers and Cables Added a water pan and float to the precooling module Added the current of the unit and the corresponding cable model selection Added the content a...

Page 5: ... Control Module 22 2 5 Operating Environment Specifications 24 2 6 Technical Specifications 26 2 7 Working Modes 27 3 System Installation Building Scenario 30 3 1 Installation Requirements 30 3 1 1 Installation Precautions 30 3 1 2 Maintenance Space 31 3 1 3 Storage 32 3 2 Materials 32 3 2 1 Installation Tools 32 3 2 2 Water Refill Pipe and Drainpipe 34 3 2 3 Pipe Support 35 3 2 4 Cable 36 3 3 Ins...

Page 6: ... Installing Electric Heater Components and Cables 61 4 System Installation FDC Scenario 64 4 1 Installation Requirements 64 4 1 1 Installation Precautions 64 4 1 2 Maintenance Space 65 4 1 3 Storage 66 4 2 Materials 66 4 2 1 Installation Tools 66 4 2 2 Water Refill Pipe and Drainpipe 68 4 2 3 Pipe Support 69 4 2 4 Cable 70 4 3 Installing a FusionCol8000 E 71 4 3 1 Unpacking and Checking 71 4 3 2 S...

Page 7: ... 6 4 4 1 Setting Communications Parameters Modbus RTU Protocol 116 6 4 4 2 Setting Communications Parameters Modbus TCP Protocol 116 6 4 4 3 Setting Communications Parameters SNMP Protocol 119 6 4 5 Optional Setting WIFI Parameters 123 6 5 Startup 123 6 6 Wizard Startup 127 6 7 Power Off 128 6 8 Checking After Commissioning 129 7 WebUI 130 7 1 Preparations and WebUI Login 130 7 2 Introduction to t...

Page 8: ...215 8 5 15 4 2 Vacuumizing 215 8 5 15 4 3 Precharging Refrigerant 216 8 5 15 5 Charging the Remaining Refrigerant 218 8 5 16 Replacing a Filter Dryer 219 8 5 17 Replacing a Compressor Drive 221 8 5 18 Replacing a Fan Drive 223 8 5 19 Replacing a Liquid Level Sensor 224 8 5 20 Replacing a Water Pump 226 8 5 21 Replacing a Switch 227 8 5 22 Replacing a Contactor 229 8 5 23 Replacing an SPD 230 8 5 2...

Page 9: ...tificate 249 9 2 3 How Do I View Active Alarms and Historical Alarms 250 9 2 4 How Do I Export or Import a Configuration File 250 9 2 5 How Do I Export Fault Information 251 9 2 6 How Do I Change an IP Address 251 9 2 7 How Do I View Version Information 252 A Cleaning the Device 253 B Repairing Paint 254 C Parameter Description 259 D Cooling System Layout 271 E Electrical Conceptual Diagrams 272 F...

Page 10: ...llow local laws and regulations when installing operating or maintaining the equipment The safety instructions in this document are only supplements to local laws and regulations Huawei will not be liable for any consequences of the following circumstances Operation beyond the conditions specified in this document Installation or use in environments which are not specified in relevant internationa...

Page 11: ...tion operation and maintenance Before handling a conductor surface or terminal measure the contact point voltage and ensure that there is no risk of electric shock After installing the equipment remove idle packing materials such as cartons foam plastics and cable ties from the equipment area In the case of a fire immediately leave the building or the equipment area and turn on the fire alarm bell...

Page 12: ...d during equipment transportation or installation in a timely manner Equipment with scratches cannot be exposed to an outdoor environment for a long period of time Before operations ensure that the equipment is firmly secured to the floor or other solid objects such as a wall or an installation rack Do not use water to clean electrical components inside or outside of a cabinet Do not change the st...

Page 13: ...ssionals personnel who are trained or experienced in equipment operations and are clear of the sources and degree of various potential hazards in equipment installation operation maintenance Trained personnel personnel who are technically trained have required experience are aware of possible hazards on themselves in certain operations and are able to take protective measures to minimize the hazar...

Page 14: ...ilities must be performed by qualified personnel Cabling When routing cables ensure that a distance of at least 30 mm exists between the cables and heat generating components or areas This prevents damage to the insulation layer of the cables Do not route cables behind the air intake and exhaust vents of the equipment Ensure that cables meet the VW 1 or ZB flame spread rating requirements or highe...

Page 15: ...kaging materials before storing or transporting them Figure 1 1 Wearing an ESD wrist strap Neutral Ground Voltage It is recommended that the three phase loads be equalized and the neutral ground voltage be kept at less than 2 V to meet power distribution requirements 1 4 Installation Environment Requirements To prevent fire due to high temperature ensure that the ventilation vents or heat dissipat...

Page 16: ...s Wear personal protective equipment such as the safety helmet and safety belt or waist rope and fasten it to a solid structure Do not mount it on an insecure moveable object or metal object with sharp edges Make sure that the hooks will not slide off Set a restricted area and eye catching signs for working at heights to warn away irrelevant personnel Carry the operation machinery and tools proper...

Page 17: ...fiberglass ladders when you need to perform live working at heights When a step ladder is used ensure that the pull ropes are secured and the ladder is held firm Before using a ladder check that it is intact and confirm its load bearing capacity Do not overload it Ensure that the ladder is securely positioned The recommended angle for a ladder against the floor is 75 degrees as shown in the follow...

Page 18: ...es inside Metal shavings from drilling may short circuit boards inside the equipment Obtain the consent from the customer and subcontractor before drilling Wear goggles and protective gloves when drilling holes When drilling holes protect the equipment from shavings After drilling clean up any shavings that have accumulated inside or outside the equipment Moving Heavy Objects DANGER When removing ...

Page 19: ...tem Safety Welding At least two persons are required on a welding site A welder must have a work permit A welding site must be free from inflammables Ensure that a fire extinguisher wet wiper and water container are available A burning welding torch must not be placed on a component or on the floor and must not be placed in a metal container with acetylene and oxygen Otherwise the gas may leak and...

Page 20: ...h other wastes that have a shell in European Union EU areas To avoid environment pollution and harm to human health wastes must be classified and recycled This also promotes resource reuse When recycling a device fill in the device information in the recycling collection system or contact your dealer for help The dealer can help you recycle devices in a safe and environment friendly way 1 7 Others...

Page 21: ...enter smart cooling 2 Model series 8000 modular indirect evaporative cooling system 3 Cooling mode E indirect evaporative cooling 4 Model code 240 model code 240 5 Air supply mode H horizontal flow 6 Power supply 4 380 415 V three phase 50 60 Hz 2 2 Product Composition FusionCol8000 E240 Modular Indirect Evaporative Cooling System User Manual 2 Product Description Issue 02 2021 04 15 Copyright Hua...

Page 22: ... Maintenance door 4 Maintenance door 5 Electric control box 6 Outdoor air exhaust vent end 7 Indoor air return vent top 8 Outdoor air intake vent side Figure 2 3 Components interior FusionCol8000 E240 Modular Indirect Evaporative Cooling System User Manual 2 Product Description Issue 02 2021 04 15 Copyright Huawei Technologies Co Ltd 13 ...

Page 23: ...tic pressure high reliability and a long service life The fan is separated from the drive The fan efficiency is improved by more than 8 compared with a common EC fan The direct drive that the fan adopts has higher transmission efficiency than the belt drive which reduces belt replacement and routine checks 6 Evaporat or The synergy field principle and computational fluid dynamics CFD are used to o...

Page 24: ...me to facilitate fault locating 11 Liquid level sensor Liquid level sensor at the bottom of the precooling module A high liquid level sensor is added under the precooling module If the precooling module is abnormal an alarm is generated in advance Liquid level sensor inside the spray water tank There are three liquid level sensors in the spray water tank which are associated with the water refill ...

Page 25: ...tric control box 6 Maintenance door 7 Outdoor air exhaust vent end 8 Outdoor air exhaust vent top 9 Indoor air return vent side NOTE The outdoor air exhaust vent is selected based on the actual situation Figure 2 5 Components interior FusionCol8000 E240 Modular Indirect Evaporative Cooling System User Manual 2 Product Description Issue 02 2021 04 15 Copyright Huawei Technologies Co Ltd 16 ...

Page 26: ...ic pressure high reliability and a long service life The fan is separated from the drive The fan efficiency is improved by more than 8 compared with a common EC fan The direct drive that the fan adopts has higher transmission efficiency than the belt drive which reduces belt replacement and routine checks 6 Evaporator The synergy field principle and computational fluid dynamics CFD are used to opt...

Page 27: ... into one device to save space in the smart cooling product and improve efficiency The compressor drive is controlled over RS485 You can view the drive running status and parameters on the display module in real time to facilitate fault locating 11 Liquid level sensor Liquid level sensor at the bottom of the precooling module A high liquid level sensor is added under the precooling module If the p...

Page 28: ...and locate a fault 2 3 Display Module Appearance The display module provides a 7 inch true color touchscreen that provides man machine interfaces for query setting monitoring and maintenance Figure 2 6 Display module 1 Indicator 2 I2C 12V reserved 3 DP port display port connected to the main control module 4 SW reserved Table 2 1 Indicator and buzzer status description Indicator Buzzer Running Sta...

Page 29: ...d fan normal faulty Telecontrol startup shutdown Teamwork When multiple units work cooperatively the controller optimally distributes the heat load to reduce power consumption and provides backup to improve reliability Backup When a unit in the group is faulty the backup unit starts to operate automatically improving system reliability Rotation Each unit enters the active mode one by one periodica...

Page 30: ... panel is protected by a multi level password protection mechanism to avoid misoperation The password is verified each time the system is started or shut down to ensure system operation security The controller provides functions such as automatic recovery after power failure and water leakage detection improving the system reliability The cooling capacity air volume as well as the operating status...

Page 31: ...Off There is no alarm or a warning or minor alarm is generated Steady red There is a major or critical alarm Communications Ports FE_1 and FE_2 ports connect FE MAC_CAN teamwork communications cables CAN_IN and CAN_OUT ports connect CAN teamwork and RS485 monitoring cascading communications cables RS485 12V port connects a temperature and humidity T H sensor COM FE port connects a monitoring commu...

Page 32: ...ployment View or obtain running information about the smart cooling product during inspection Only Huawei service engineers or authorized service engineers are allowed to use the WiFi module To ensure security remove the WiFi module immediately after use Connects a USB flash drive to export data import and export configuration files import certificates and keys and upgrade the version DP port conn...

Page 33: ...e 40 C to 70 C Storage humidity 5 95 RH Altitude The performance is not derated when the altitude is below 1000 m and is derated when the altitude ranges from 1000 m to 4000 m Table 2 3 Derating coefficients Altitude m 0 100 0 1000 1500 200 0 2500 3000 3500 4000 Air volume coefficient 1 0 887 0 835 0 78 5 0 737 0 692 0 649 0 608 Cooling capacity coefficient 1 0 887 0 835 0 78 5 0 737 0 692 0 649 0...

Page 34: ...king conditions Water quality Specific requirements Filtering level 89 μm 5 Ph 8 5 Conductivity 1300 μS cm Total hardness 100 mg L Total alkalinity 200 mg L Chloride 250 mg L Organic matter 3 mg L Silicon dioxide 10 mg L NOTE If the water quality does not meet the requirements the precooling module maintenance frequency increases Power distribution Leakage circuit breakers are not recommended for ...

Page 35: ...m x 2438 mm x 4700 mm 4150 mm x 2438 mm x 6058 mm Installation scenario Indoor FDC Power system 380 415 V AC 3 phase 50 Hz 60 Hz Air filter level on the indoor air return side EN 779 G4 Air filter level on the outdoor air intake side EN 779 G3 Fan type EC Air volume Indoor 55 000 m3 h Outdoor 50 000 m3 h Net weight 5000 kg 11 000 kg Operating weight 5500 kg 11 500 kg FusionCol8000 E240 Modular Ind...

Page 36: ...Specifications Compressor type Variable frequency scroll compressor Number of compressors 3 Throttling device Electronic expansion valve EEV Refrigerant R410A 2 7 Working Modes The unit runs in one of the following modes based on the real time working conditions and load Table 2 7 Cooling modes Cooling Mode Fan Status Water Pump Status Compressor Status Dry mode fan On Off Off Wet mode fan sprayin...

Page 37: ... Figure 2 9 Wet mode Figure 2 10 Dry mode auxiliary cooling mode FusionCol8000 E240 Modular Indirect Evaporative Cooling System User Manual 2 Product Description Issue 02 2021 04 15 Copyright Huawei Technologies Co Ltd 28 ...

Page 38: ...Figure 2 11 Wet mode auxiliary cooling mode FusionCol8000 E240 Modular Indirect Evaporative Cooling System User Manual 2 Product Description Issue 02 2021 04 15 Copyright Huawei Technologies Co Ltd 29 ...

Page 39: ... drainage ditches with sufficient drainage capacity NOTICE The layout and installation of pipes should facilitate the maintenance of the unit Checking Electrical Access for Auxiliaries NOTICE The modular indirect evaporative cooling system is an important air handling unit AHU You need to strictly follow the heating ventilating and air conditioning HVAC construction requirements To ensure proper o...

Page 40: ...valves and connectors At low temperatures take thermal insulation measures to prevent water pipes from freezing 3 1 2 Maintenance Space Reserve sufficient space around the equipment for operation and ventilation Figure 3 1 Maintenance space not combined unit mm 1 Wall 2 Indoor air supply vent end 3 Electric control box Figure 3 2 Maintenance space combined unit mm 1 Wall 2 Indoor air supply vent e...

Page 41: ...nd them in the fittings delivered with the equipment Pay attention to the type and quantity of materials in the packing list Auxiliary material Customers can purchase this type of materials from Huawei or other vendors Cables Optional material Purchased from Huawei based on application scenarios Temperature and humidity sensor water sensor and smoke sensor Engineering purchase material This type o...

Page 42: ...Pipe wrench ESD gloves Wire strippers Needle nose pliers Diagonal pliers Pliers Flashlight Measuring tape Step ladder Marker Insulation tape Hammer drill Diesel forklift Manual pallet truck Lifting rope Rubber hose Alcohol FusionCol8000 E240 Modular Indirect Evaporative Cooling System User Manual 3 System Installation Building Scenario Issue 02 2021 04 15 Copyright Huawei Technologies Co Ltd 33 ...

Page 43: ...nical Specification for the Application of Anaerobic Glue in Engineering Machinery 3 2 2 Water Refill Pipe and Drainpipe Table 3 3 Pipe specifications Item Connector Dimensions Material Descriptio n Water tank refill pipe G 3 4 inch external thread connector DN25 Rigid pipe made of PP R C PVC or other materials Engineerin g purchase is required and specificati ons are determine d based on engineer...

Page 44: ...pipes as shown in the figure The actual appearance of the supports will be different based on onsite situations Figure 3 3 Pipe supports unit mm NOTE The height of the U shaped pipe clamp is 5 mm less than the pipe diameter including the thermal insulation foam Install a support every 2500 mm for the straight sections of pipes and 1000 mm away from each bending point in turning sections FusionCol8...

Page 45: ...l area L1 3 x 70 mm2 L2 L3 PE 35 mm2 Standby input Recommend ed cable cross sectional area L1 3 x 70 mm2 L2 L3 PE 35 mm2 NOTE The onsite grounding resistance must comply with related standards When selecting connecting and routing cables follow local safety regulations and rules When the external conditions such as the cable layout or ambient temperatures change perform verification in accordance ...

Page 46: ...ge is found notify the carrier immediately Step 2 Remove the plastic packaging materials Step 3 Check the types and quantity of fittings according to the fitting list If any fitting is missing contact Huawei technical support End 3 3 2 Securing a Smart Cooling Product Prerequisites NOTICE The evenness of concrete platforms is critical to device installation Ensure that the height altitude differen...

Page 47: ...than or equal to 5 degrees Lift and land a device slowly to prevent shock to equipment inside it Remove the steel ropes after ensuring that the device is placed evenly on the concrete platforms Tools marker ink fountain long leather measuring tape crane socket wrench torque wrench Phillips screwdriver jack steel hoisting rope level level gauge hammer drill angle ruler claw hammer vacuum cleaner Ma...

Page 48: ...unting positions for corner fittings ensure that the four lines form a rectangle Step 4 Adjust the device in the required direction connect the steel hoisting ropes and hoist the device onto the concrete platforms NOTICE When hoisting a device ensure that the four corner fittings of the device are aligned with the marked mounting positions for corner fittings on the concrete platforms FusionCol800...

Page 49: ...latforms Step 6 Install the equipotential ground cable or ground lug Ground lug engineering procurement Use hot dip zinc coated flat steel sheet with a cross sectional area of 40 mm x 4 mm FusionCol8000 E240 Modular Indirect Evaporative Cooling System User Manual 3 System Installation Building Scenario Issue 02 2021 04 15 Copyright Huawei Technologies Co Ltd 40 ...

Page 50: ...elect the nearest one Figure 3 8 Installing the ground cable or ground lug 1 Ground cable 2 Ground lug End Follow up Procedure After the device is hoisted and installed verify the installation to ensure normal use of products and smooth subsequent installation FusionCol8000 E240 Modular Indirect Evaporative Cooling System User Manual 3 System Installation Building Scenario Issue 02 2021 04 15 Copy...

Page 51: ...move the adjustable side panels for the compressor Step 2 Check whether any of the needle valve bonnets shown in Figure 3 9 is missing 1 If any bonnet is missing contact Huawei technical support 2 If no bonnet is missing remove the valve bonnets and press the valve plugs using the valve bonnets in turn If gas flows out the system is normal If no gas flows out contact Huawei technical support Figur...

Page 52: ...OTE The indoor supply air duct is used as an example The air duct position in the figure is for reference only Figure 3 10 Installing a supply air duct NOTE The air duct must be wrapped with thermal insulation foam and the thickness of the thermal insulation foam must be greater than or equal to 3 cm The joint between the air duct and the unit should be sealed to prevent air leakage Generally the ...

Page 53: ...utlet pipes Do not let external impurities enter the pipes The water inlet and outlet pipes of the unit are connected using screw threads Do not exert excessive force when connecting the pipes to avoid damaging the pipes Use two pipe pliers or chain pliers to connect pipes Water pipes need to be prepared onsite If galvanized steel pipes are used stainless steel connectors must be used to ensure se...

Page 54: ... pan drainpipe evaporator condensate water pan drainpipe and water tank drainpipe Remove the sheet metal for drainpipes Install the drainpipe Figure 3 13 Installing the drainpipe Step 2 Install the floor drain drainpipe Figure 3 14 Installing the drainpipe FusionCol8000 E240 Modular Indirect Evaporative Cooling System User Manual 3 System Installation Building Scenario Issue 02 2021 04 15 Copyrigh...

Page 55: ...t 3 cm End Sealing 1 Remove the paper protective film from the sealing putty 2 Seal the gaps between the water pipes and the devices using sealing putty after the pipes are correctly connected Figure 3 15 Setting sealing putty 1 Paper protective film 2 Sealing putty standard configuration Pipe Anti freezing Condensate drainpipes and water refill pipes may freeze and thereby be blocked or crack in ...

Page 56: ...ntenance door Wrap the electric heating belt and then wrap the thermal insulation foam Ensure that the thermal insulation foam covers the temperature control switch and temperature sensor probe The thermal insulation foam must withstand a temperature above 200 C 3 3 6 Removing Transport Fasteners and Desiccant Bags Procedure Step 1 Remove the maintenance door of the compressor and take out the des...

Page 57: ...anels for the compressor End 3 4 Installing Cables 3 4 1 Precautions Connections of all power cables control cables and ground cables must comply with local electrical regulations and the cable specifications should comply with local cabling specifications For details about the maximum current see the device nameplate Check that the input voltage and frequency of the primary power supply meet the ...

Page 58: ...y air damper cable 4 Electric heater controller cable 5 Signal cable 3 4 3 Optional Installing Signal Cables Prerequisites Signal cables must be routed through protective tubes for protection The device can be connected to a smoke sensor remote startup shutdown signal public alarm signal and water sensor The following describes how to connect a water sensor Context Figure 3 20 Signal cable termina...

Page 59: ...h air exhaust damper 24 V DC 6 Common alarm 1 Fresh air damper Y control Indoor supply air damper GND Fresh air exhaust damper GND 7 Common alarm 2 Reserved Indoor supply air damper U feedback Fresh air exhaust damper U feedback 8 Common alarm 2 Reserved Indoor supply air damper Y control Fresh air exhaust damper Y control Procedure Step 1 Connect one end of the water sensor cable to the water sen...

Page 60: ...th between adjacent devices must be less than or equal to 100 m and the distance for CAN teamwork communication must be less than or equal to 310 m Route cables in compliance with local standards Take appropriate shielding measures such as using a galvanized pipe or an ELV cable tray to reduce the impact of electromagnetic interference on teamwork communication Otherwise teamwork networking may fa...

Page 61: ...3 RS485 monitoring communications cable 4 Blue 5 White and blue End 3 4 4 2 CAN Teamwork RS485 Monitoring Step 1 Connect teamwork and monitoring communications cables Networking Teamwork Monitoring Protocol CAN Modbus RTU FusionCol8000 E240 Modular Indirect Evaporative Cooling System User Manual 3 System Installation Building Scenario Issue 02 2021 04 15 Copyright Huawei Technologies Co Ltd 52 ...

Page 62: ...e not grouped n 1 set RS485 monitoring grouping to Enable on the Modbus Settings screen for each device If devices are grouped n 1 recommended n 4 set RS485 monitoring grouping to Enable on the Modbus Settings screen for the device with the COM FE port connected NOTE Connect the COM FE port on the main control module of the last smart cooling product in each group to the RS485 port on the host Cus...

Page 63: ...t cooling products set Enable teamwork CAN resistor to Yes NOTE Customers can purchase Huawei s switch and NetEco for the monitoring system Figure 3 25 Connecting communications cables End 3 4 4 4 FE Teamwork RS485 Monitoring Step 1 Connect teamwork and monitoring communications cables Networking Teamwork Monitoring Protocol MAC_CAN Modbus RTU FusionCol8000 E240 Modular Indirect Evaporative Coolin...

Page 64: ...ettings screen for each device If devices are grouped n 1 recommended n 4 set RS485 monitoring grouping to Enable on the Modbus Settings screen for the device with the COM FE port connected NOTE Connect the COM FE port on the main control module of the last smart cooling product in each group to the RS485 port on the host Customers can purchase Huawei s ECC and NetEco for the monitoring system Fig...

Page 65: ...ng Power Cables Procedure Step 1 Route power cables through the external cable holes Step 2 Open the electric control box outside the unit Step 3 Connect one end of the primary and backup power cables to the primary backup power supply terminals PE terminal through the cable holes in the electric control box of the unit and connect the other end to the power supply Figure 3 28 Connecting power cab...

Page 66: ...shows how to fill a gap using sealing putty Figure 3 29 Filling the hole with sealing putty 1 Paper protective film 2 Sealing putty standard configuration End 3 5 Installing an Air Deflector Procedure Step 1 Assemble an air deflector Figure 3 30 Assembling an air deflector FusionCol8000 E240 Modular Indirect Evaporative Cooling System User Manual 3 System Installation Building Scenario Issue 02 20...

Page 67: ... an air deflector Step 3 Optional If an air damper is configured install the assembled air deflector on the air damper Figure 3 33 Installing an air deflector End FusionCol8000 E240 Modular Indirect Evaporative Cooling System User Manual 3 System Installation Building Scenario Issue 02 2021 04 15 Copyright Huawei Technologies Co Ltd 58 ...

Page 68: ...hat the total length of the cable required for the T H sensors outside the cabinet be less than or equal to 150 m If the cable length is greater than 120 m obtain 12 V DC power from the site to supply power to the T H sensors that are 120 m or further away from the cabinet Ensure that the input voltage of each T H sensor ranges from 9 V to 16 V The T H sensors outside the cabinet must be connected...

Page 69: ... ON OFF ON OFF Hot aisle 3 temp humid 23 ON ON ON OFF ON OFF Hot aisle 4 temp humid 24 OFF OFF OFF ON ON OFF Hot aisle 5 temp humid 25 ON OFF OFF ON ON OFF Hot aisle 6 temp humid 26 OFF ON OFF ON ON OFF NOTICE The default T H sensor address is 1 Keep the last RS485_R DIP switch at OFF After the addresses are set power on the device choose Settings System Settings T H sensor on the home screen of t...

Page 70: ...the maintenance of the unit Cables must be protected against damage Step 3 Connect the air damper cable terminal and air damper actuator terminal Figure 3 34 Terminal connection End 3 8 Optional Installing Electric Heater Components and Cables Electric heater components include the electric heating belt temperature sensor probe transformer and electric heater controller FusionCol8000 E240 Modular ...

Page 71: ...DF and secure it using screws Figure 3 35 Transformer position Step 3 Install the electric heater controller Figure 3 36 Installing the electric heater controller 1 Electric heater controller 2 Sheet metal FusionCol8000 E240 Modular Indirect Evaporative Cooling System User Manual 3 System Installation Building Scenario Issue 02 2021 04 15 Copyright Huawei Technologies Co Ltd 62 ...

Page 72: ...through the condensate drainage hole wrap the heating belt around the condensate drainpipe and ensure that the temperature sensor probe is closely attached to the drainpipe Step 6 Use silicone sealant to seal the gaps between the heating belt cables pipe and wall panels Step 7 Use thermal insulation foam to wrap the heating belt and temperature sensor probe around the pipe Step 8 Press the SET but...

Page 73: ... drainage ditches with sufficient drainage capacity NOTICE The layout and installation of pipes should facilitate the maintenance of the unit Checking Electrical Access for Auxiliaries NOTICE The modular indirect evaporative cooling system is an important air handling unit AHU You need to strictly follow the heating ventilating and air conditioning HVAC construction requirements To ensure proper o...

Page 74: ...w temperatures take thermal insulation measures to prevent water pipes from freezing 4 1 2 Maintenance Space Reserve sufficient space around the equipment for operation and ventilation Figure 4 1 Maintenance space not combined unit mm 1 Wall 2 Side of the indoor air return vent end 3 Electric control box 4 Corridor module Figure 4 2 Maintenance space combined unit mm 1 Wall 2 Side of the indoor ai...

Page 75: ... find them in the fittings delivered with the equipment Pay attention to the type and quantity of materials in the packing list Auxiliary material Customers can purchase this type of materials from Huawei or other vendors Cables Optional material Purchased from Huawei based on application scenarios Temperature and humidity sensor water sensor and smoke sensor Engineering purchase material This typ...

Page 76: ...ch Pipe wrench ESD gloves Wire strippers Needle nose pliers Diagonal pliers Pliers Flashlight Measuring tape Step ladder Marker Insulation tape Hammer drill Diesel forklift Manual pallet truck Lifting rope Rubber hose Alcohol FusionCol8000 E240 Modular Indirect Evaporative Cooling System User Manual 4 System Installation FDC Scenario Issue 02 2021 04 15 Copyright Huawei Technologies Co Ltd 67 ...

Page 77: ...echnical Specification for the Application of Anaerobic Glue in Engineering Machinery 4 2 2 Water Refill Pipe and Drainpipe Table 4 3 Pipe specifications Item Connector Dimensions Material Descriptio n Water tank refill pipe G 3 4 inch external thread connector DN25 Rigid pipe made of PP R C PVC or other materials Engineerin g purchase is required and specificati ons are determine d based on engin...

Page 78: ...er pipes as shown in the figure The actual appearance of the supports will be different based on onsite situations Figure 4 3 Pipe supports unit mm NOTE The height of the U shaped pipe clamp is 5 mm less than the pipe diameter including the thermal insulation foam Install a support every 2500 mm for the straight sections of pipes and 1000 mm away from each bending point in turning sections FusionC...

Page 79: ...onal area L1 3 x 70 mm2 L2 L3 PE 35 mm2 Standby input Recommend ed cable cross sectional area L1 3 x 70 mm2 L2 L3 PE 35 mm2 NOTE The onsite grounding resistance must comply with related standards When selecting connecting and routing cables follow local safety regulations and rules When the external conditions such as the cable layout or ambient temperatures change perform verification in accordan...

Page 80: ... FusionCol8000 E 4 3 1 Unpacking and Checking Procedure Step 1 Verify that the package is intact If any damage is found notify the carrier immediately Step 2 Remove the plastic packaging materials Step 3 Check the types and quantity of fittings according to the fitting list If any fitting is missing contact Huawei technical support End FusionCol8000 E240 Modular Indirect Evaporative Cooling System...

Page 81: ...side Procedure Step 1 Connect the hoisting ropes and hoist the equipment to the installation area NOTE It is recommended that a crane with a lifting capacity greater than or equal to 15 t be used for transportation FusionCol8000 E240 Modular Indirect Evaporative Cooling System User Manual 4 System Installation FDC Scenario Issue 02 2021 04 15 Copyright Huawei Technologies Co Ltd 72 ...

Page 82: ...ual scenario Step 3 Secure the corner fitting box of the unit on the side of the indoor air supply vent end Step 4 Open the maintenance door and enter the cabinet to secure the corner fitting box FusionCol8000 E240 Modular Indirect Evaporative Cooling System User Manual 4 System Installation FDC Scenario Issue 02 2021 04 15 Copyright Huawei Technologies Co Ltd 73 ...

Page 83: ...r securing the unit inside the cabinet Step 5 Hoist the other device Step 6 Place the device on the top of the installed device ensure that the contact surface is clean Step 7 Secure the corner fitting boxes FusionCol8000 E240 Modular Indirect Evaporative Cooling System User Manual 4 System Installation FDC Scenario Issue 02 2021 04 15 Copyright Huawei Technologies Co Ltd 74 ...

Page 84: ... needle valve bonnets shown in Figure 4 8 is missing 1 If any bonnet is missing contact Huawei technical support 2 If no bonnet is missing remove the valve bonnets and press the valve plugs using the valve bonnets in turn If gas flows out the system is normal If no gas flows out contact Huawei technical support FusionCol8000 E240 Modular Indirect Evaporative Cooling System User Manual 4 System Ins...

Page 85: ...in the figure is for reference only Indoor return air duct end secured using 34 M8x20 screws Indoor return air duct side secured using 48 M8x20 screws Indoor supply air duct secured using 40 M8x20 screws Procedure Step 1 Install an air duct NOTE The following describes how to install an indoor supply air duct Figure 4 9 Installing a return air duct FusionCol8000 E240 Modular Indirect Evaporative C...

Page 86: ...trap must meet the requirements specified in Figure 3 11 Figure 4 10 Designed height of the water trap NOTE It is recommended that the height of segment B be a smaller value Installing Water Pipes Water pipes need to be prepared onsite If galvanized steel pipes are used stainless steel connectors must be used to ensure sealing After water pipes are installed wrap thermal insulation foam Figure 4 1...

Page 87: ...it are connected using pipe screw threads Do not exert excessive force when connecting the pipes to avoid damaging the pipes Use two pipe pliers or chain pliers to connect pipes The water pipes are connected using thread connectors The threaded joints must be sealed with sealing tape or thread adhesive When connecting water pipes use appropriate active connectors and secure them using a wrench The...

Page 88: ...zing measures for the pipes Wrap the pipes starting from the water refill and drainage ports to the frozen soil layer with an electric heating belt Bury the remaining pipes underground the temperature at a specific depth underground is always above 0 C Figure 4 15 Pipe anti freezing solution 1 Electric heating belt 2 Water refill pipe 3 Drainpipe connected to the utility drainpipes 4 Soil FusionCo...

Page 89: ...adjustable side panel of the compressor and take out the desiccant bag from the compressor Step 2 Open the electric control box and take out the desiccant bag from the box Step 3 Open the outdoor intake air filter and take out the desiccant bag from the outdoor air intake compartment Step 4 Open the adjustable side panel and water barrier of the spray pump and take out the two desiccant bags from ...

Page 90: ...ut voltage and frequency of the primary power supply meet the requirements Only trained and qualified personnel are allowed to connect cables Before connecting cables use a multimeter to measure the input voltage and ensure that the power supply is disconnected All smart cooling products must be securely grounded before being powered on Cables should be securely connected and free of contact with ...

Page 91: ...or Water sensor Outdoor exhaust air damper GND Indoor return air damper GND 3 Remote startup shutdown Fresh air damper 24 V DC Outdoor exhaust air damper U feedback Indoor return air damper U feedback 4 Remote startup shutdown Fresh air damper GND Outdoor exhaust air damper Y control Indoor return air damper Y control 5 Common alarm 1 Fresh air damper U feedback Indoor supply air damper 24 V DC Fr...

Page 92: ...ignal cable hole at the bottom of the electric control box Step 3 Connect the signal cable to X502 terminals 1 and 2 NOTICE If a water sensor rope type is to be connected connect the signal cable to terminals X201 and X202 Figure 4 19 Ports for a water sensor rope type End FusionCol8000 E240 Modular Indirect Evaporative Cooling System User Manual 4 System Installation FDC Scenario Issue 02 2021 04...

Page 93: ...cable length between adjacent devices must be less than or equal to 100 m and the maximum distance for CAN teamwork communication must be less than or equal to 310 m Route cables in compliance with local standards Take appropriate shielding measures such as using a galvanized pipe or an ELV cable tray to reduce the impact of electromagnetic interference on teamwork communication Otherwise teamwork...

Page 94: ...4 22 RS485 monitoring communications cable 4 Blue 5 White and blue End 4 4 4 2 CAN Teamwork RS485 Monitoring Step 1 Connect teamwork and monitoring communications cables Networking Teamwork Monitoring Protocol CAN Modbus RTU FusionCol8000 E240 Modular Indirect Evaporative Cooling System User Manual 4 System Installation FDC Scenario Issue 02 2021 04 15 Copyright Huawei Technologies Co Ltd 85 ...

Page 95: ... are not grouped n 1 set RS485 monitoring grouping to Enable on the Modbus Settings screen for each device If devices are grouped n 1 recommended n 4 set RS485 monitoring grouping to Enable on the Modbus Settings screen for the device with the COM FE port connected NOTE Connect the COM FE port on the main control module of the last smart cooling product in each group to the RS485 port on the host ...

Page 96: ...art cooling products set Enable teamwork CAN resistor to Yes NOTE Customers can purchase Huawei s switch and NetEco for the monitoring system Figure 4 24 Connecting communications cables End 4 4 4 4 FE Teamwork RS485 Monitoring Step 1 Connect teamwork and monitoring communications cables Networking Teamwork Monitoring Protocol MAC_CAN Modbus RTU FusionCol8000 E240 Modular Indirect Evaporative Cool...

Page 97: ... Settings screen for each device If devices are grouped n 1 recommended n 4 set RS485 monitoring grouping to Enable on the Modbus Settings screen for the device with the COM FE port connected NOTE Connect the COM FE port on the main control module of the last smart cooling product in each group to the RS485 port on the host Customers can purchase Huawei s ECC and NetEco for the monitoring system F...

Page 98: ...lling Power Cables Procedure Step 1 Route power cables through the external cable holes Step 2 Open the electric control box outside the unit Step 3 Connect one end of the active and standby power cables to the active standby power supply terminals PE terminal through the cable holes in the electric control box of the unit and connect the other end to the power supply Figure 4 27 Connecting power ...

Page 99: ...ag The following figure shows how to fill a gap using sealing putty Figure 4 28 Fill the holes with sealing putty 1 Paper protective film 2 Sealing putty standard configuration End 4 5 Installing an Air Deflector Procedure Step 1 Assemble an air deflector FusionCol8000 E240 Modular Indirect Evaporative Cooling System User Manual 4 System Installation FDC Scenario Issue 02 2021 04 15 Copyright Huaw...

Page 100: ...sors be deployed near heat sources or near places that lack cooling capacity Place the T H sensors near the cabinet The sensors cannot face the air outlet of the device Procedure Step 1 Connect the IN port on the first T H sensor outside the cabinet to the RS485 12V port on the main control module Step 2 Connect the OUT port on the T H sensor outside the cabinet to the IN port on the next T H sens...

Page 101: ...han 9 V the T H sensors cannot work properly Step 3 Set DIP switches of the T H sensors Table 4 7 DIP switch settings on T H sensors Locatio n Display Name Addre ss DIP Switch No 1 2 3 4 5 6 Air return side Return air 2 temp humid 1 ON OFF OFF OFF OFF OFF Outdoor intake air Outdoor intake air 1 temp humid 31 ON ON ON ON ON OFF Outdoor intake air 3 temp humid 32 OFF OFF OFF OFF OFF ON Cold aisle Co...

Page 102: ... screen of the display module and set the sensors in the aisles corresponding to the addresses to Enable Otherwise the sensors will not work End 4 7 Optional Installing Electric Heater Components and Cables Electric heater components include the electric heating belt temperature sensor probe and electric heater controller Procedure Step 1 Remove the exhaust side panel Step 2 Install the electric h...

Page 103: ...able length is about 11 m and the cable specification is 3 x 1 5 mm2 Step 5 Route the heating belt and temperature sensor probe through the condensate drainage hole wrap the heating belt around the condensate drainpipe and ensure that the temperature sensor probe is closely attached to the drainpipe Step 6 Use silicone sealant to seal the gaps between the heating belt cables pipe and wall panels S...

Page 104: ...s Within 10s press and to set the parameter to 5 C and press the SET button to save the setting End FusionCol8000 E240 Modular Indirect Evaporative Cooling System User Manual 4 System Installation FDC Scenario Issue 02 2021 04 15 Copyright Huawei Technologies Co Ltd 95 ...

Page 105: ...ed Failed The water filter is secured Passed Failed The liquid level sensor moves flexibly Passed Failed The water inlet pipe is connected securely without leakage Passed Failed The water tank is free of sundries inside and its filter is unblocked Passed Failed Compres sor The sheet metal fasteners on the compressor have been removed Passed Failed The bolts for securing the compressor are tightene...

Page 106: ...les for the unit are connected as required Passed Failed The rated specifications of the upstream general switch meet the maximum current requirement Passed Failed All cables connectors and screws are secured Passed Failed The device is properly grounded Passed Failed Table 5 3 Pipe checklist Expected Result Check Result All pipes are secured Passed Failed All pipes are wrapped with thermal insula...

Page 107: ...res are connected to the device in correct phase sequence Step 4 If teamwork networking is required verify that the teamwork cable is correctly connected Step 5 If the cabinet is connected to the temperature and humidity sensor check that the cable connection and DIP switch settings are correct End 6 2 Power On Procedure Step 1 Turn on the main switch of the unit For a device with dual power suppl...

Page 108: ...or before modifying parameters Confirm with Huawei technical support before modifying parameters which cannot be modified by user operator Otherwise Huawei will not be liable for any consequences of the modification performed by the user Only certified professionals are allowed to modify advanced parameters of smart cooling products Unauthorized modifications can result in smart cooling product ma...

Page 109: ...his parameter should be the same for all units in the same teamwork group System address Set the planned unit address NOTE The addresses of units in the same teamwork group cannot be the same Teamwork function Enables or disables the teamwork function If the function is disabled the unit operates independently If it is enabled the unit operates in a team with other units NOTE Set this parameter ba...

Page 110: ...or intake air sensor 3 Outdoor intake air sensor can be set to Enable or Disable Cold aisle temperature and humidity sharing This parameter can be set to Enable or Disable Hot aisle temperature and humidity sharing This parameter can be set to Enable or Disable Supply air damper Supply air damper can be set to Enable or Disable Return air damper Return air damper can be set to Enable or Disable Ex...

Page 111: ...are advised to retain the default value Wet mode startup temperature This parameter is displayed when Balance of water and electricity consumption is set to Customized mode Set the parameter based on site requirements Dehumidifyin g function You can enable or disable the dehumidifying function NOTE If this parameter is set to Enable the device starts dehumidification when the ambient humidity is h...

Page 112: ... requirements NOTE You are advised to retain the default value Settings Quick Settings T H Sensor Temperature and humidity control type When the application scenario is non aisle containment you are advised to choose Return air Choose Cold aisle if cold aisle T H sensors are configured You are not advised to set this parameter as Hot aisle Temperature setpoint After Temperature and humidity contro...

Page 113: ...ure After power on choose Running Device Details Compressor on the home screen to view the compressor parameters and status Figure 6 2 Compressor 6 3 Home Screen The home screen of the display module displays the system status and allows you to access other function menus such as Running Alarms and Settings NOTICE The information in the screenshots is for reference only The actual parameters preva...

Page 114: ... enabled tap anywhere on the screen to mute the buzzer If a new alarm is generated after the buzzer is muted the buzzer buzzes indicates that the buzzer is disabled After the buzzer is disabled it does not buzz when an alarm is generated 5 Critical alarms Indicates the number of active critical alarms 6 Major alarms Indicates the number of active major alarms 7 Minor alarms Indicates the number of...

Page 115: ...l alarm is generated indicates that teamwork control is enabled and a teamwork control alarm is generated 6 4 Initial Configuration Log in as the admin user preset password 000001 when setting initial parameters 6 4 1 Setting Temperature and Humidity Values and Optional Enabling T H Sensors Prerequisites The T H sensors outside the cabinet need to be enabled when they are installed otherwise skip ...

Page 116: ...d humidity set points correspond to the selected control type can be set When the application scenario is cold or hot aisle containment you are advised to choose Cold aisle if the cold aisle T H sensors are configured and choose Supply air if the cold aisle T H sensors are not configured When the application scenario is non aisle containment you are advised to choose Return air and choose Cold ais...

Page 117: ...d the temperature value under this type are set the device performs cooling or heating based on the settings Set this parameter as required Return air temperature 26 35 C recommended Supply air temperature 18 24 C recommended Cold aisle temperature 18 24 C recommended Hot aisle temperature 26 35 C recommended Humidity setpoint After the temperature and humidity control type and the humidity value ...

Page 118: ...ifferential pressure sensor There is no default value Set it to 0 500 Pa Min indoor fan speed Sets the minimum speed for the indoor fan The default value is 30 You are advised not to change the value Max indoor fan speed Sets the maximum speed for the indoor fan The default value is 100 End 6 4 3 Optional Setting Teamwork Control Parameters Prerequisites The teamwork control numbers and addresses ...

Page 119: ...orking mode can be set on slave smart cooling products Other parameters of the slave units will be modified by the master unit synchronously Table 6 5 Teamwork setting Parameter Description Setting Rule Teamwork group No The number of the teamwork group This parameter should be the same for all units in the same teamwork group Set the assigned teamwork group number System address Smart cooling pro...

Page 120: ...orking mode CAN network refers to CAN teamwork networking CAN network indicates teamwork control over a CAN bus FE network indicates teamwork control over an FE port Teamwork parameter synchronizati on If Teamwork function and Teamwork parameter synchronization are both set to Enable you can select Set Local or Set Teamwork when setting parameters Set Local Set parameters for the local unit Set Te...

Page 121: ...quirements not referring to the mode delivered by the master unit When Requirement control is set to Anti competitive running the master unit synchronizes operating data the temperature and humidity control type and set points of the master unit to the slave units and all the smart cooling products in the group refer to the mode delivered by the master unit When Requirement control is Indoor fan u...

Page 122: ... by using the acquired value of the configured hot aisle T H sensor This parameter can be enabled when at least two smart cooling products in the group are configured with hot aisle T H sensors Differential pressure sharing When this parameter is enabled the smart cooling product which is not configured with the differential pressure sensor in the group is logically controlled by using the acquire...

Page 123: ...ntrol requirements Standby A standby unit responds to control requirements only if an active unit is faulty critical alarm shutdown or offline or the active unit cannot meet cooling requirements 4 M S M indicates the master unit and S indicates a slave unit A blue icon indicates that the unit is operating and a gray icon indicates that the unit is idle 5 Frame green non green A green frame indicat...

Page 124: ... actual number of devices If yes go to 2 If no check the cable connection and the teamwork settings 2 Check that the number of the running devices in the topology is the same as the actual number of devices If yes go to 3 If no check the cable connection and the teamwork settings 3 Check that the number of backup devices in the topology is the same as the actual number of devices If yes go to 4 If...

Page 125: ... as planned The NMS communicates with the smart cooling product through this address and the communication addresses of two smart cooling products connecting to the same NMS must be unique RS485 monitoring grouping Enable Disable For scenarios without grouping set this parameter to Enable for the last device For scenarios with grouping set this parameter to Enable for the last device in each teamw...

Page 126: ...egment Step 2 WAN settings On the home screen choose Settings Comm Settings WAN IP Settings and set the IP address subnet mask and gateway based on the actual plan Figure 6 9 WAN IP Settings NOTE The WAN IP address cannot be in the 192 168 245 X 192 168 246 X or 192 168 248 X network segment Step 3 On the home screen choose Settings Comm Settings Modbus Settings and set Link mode to Server and cli...

Page 127: ...oling product as a client can connect to a remote server and establish communication If you set Link mode to Server and client the smart cooling product as a server supports two client connection and establishes communication In addition the smart cooling product as a client can connect to a remote server and establish communication Client encryption Enable Disable This parameter is configurable w...

Page 128: ... you access a smart cooling product to a network management system NMS One smart cooling product supports concurrent access of up to 6 NMSs through SNMP Procedure Step 1 On the home screen choose Settings Comm Settings SNMP Settings Figure 6 11 Setting SNMP communications parameters Step 2 Set SNMP Version based on site requirements and then tap Submit If you set SNMP Version to ALL or SNMPv1 v2c ...

Page 129: ...ser Name Auth Protocol and Prop Protocol based on the actual plan MD5 and DES protocols are not secure It is recommended that you set Auth Protocol to SHA and set Prop Protocol to AES The following operations use the recommended settings as an example Figure 6 14 Setting the protocol type FusionCol8000 E240 Modular Indirect Evaporative Cooling System User Manual 6 Power On Commissioning Issue 02 2...

Page 130: ...name A password must not be a string containing duplicate sections such as 12a12a12a 3 Set SHA password and Confirm Password and tap as planned Figure 6 15 Setting an SHA password 4 Set AES password and Confirm Password as planned Figure 6 16 Setting an AES password 5 Tap Submit Step 5 Tap the text box next to SNMP Port set SNMP Port based on the actual port number tap and tap Submit FusionCol8000...

Page 131: ...4 If SNMP Version is set to SNMPv3 you need to select SNMPv3 User Name Figure 6 18 Setting SNMP trap parameters 5 Tap Submit under SNMP Trap End Follow up Procedure After a USB flash drive has been inserted into the USB port of the main control module and successfully identified tap Export File under MIB File to export the MIB file to the USB flash drive for the customer s use in accessing a third...

Page 132: ...WiFi settings Parameter Setting Method WiFi SSID Set WiFi SSID based on the actual configuration WiFi SSID is the name used for the WiFi hotspot over which a mobile phone connects to smart cooling product WiFi Password Enter the WiFi password when you use a mobile phone to connect to the WiFi The WiFi has no default password When you enable the WiFi function for the first time you need to set a pa...

Page 133: ...If you choose Settings System Settings System Control and set Require password to start or shutdown onsite to Yes a password is required for startup or shutdown if you set Require password to start or shutdown onsite to No no password is required for startup or shutdown verification Prerequisites Download the Service Expert app from HUAWEI AppGallery The app can only run on Android currently You m...

Page 134: ... start the unit Figure 6 22 Startup Step 2 Open the Service Expert app on the mobile phone NOTICE After factory settings are restored startup verification is required Step 3 Tap Startup on the home screen of the app FusionCol8000 E240 Modular Indirect Evaporative Cooling System User Manual 6 Power On Commissioning Issue 02 2021 04 15 Copyright Huawei Technologies Co Ltd 125 ...

Page 135: ...Step 4 Tap Offline Activation Figure 6 24 Generating a startup password FusionCol8000 E240 Modular Indirect Evaporative Cooling System User Manual 6 Power On Commissioning Issue 02 2021 04 15 Copyright Huawei Technologies Co Ltd 126 ...

Page 136: ...mart cooling product is started the home screen is displayed End 6 6 Wizard Startup Context Wizard startup allows you to commission the indoor fan spray system exhaust fan and cooling system and supports automatic running and judgment of components After you power on the smart cooling product for the first time the Wizard Startup screen is displayed If the smart cooling product is not started for ...

Page 137: ...the wizard startup NOTE When you enter the screen for selecting commissioning items for the first time all items are selected by default After commissioning for a component succeeds the system automatically performs commissioning for the next component you selected If commissioning fails wizard startup ends End 6 7 Power Off Context In shutdown mode the Shutdown button is green unavailable and the...

Page 138: ... Checking After Commissioning Table 6 10 Commissioning checklist Check Item Check Result The foreign matter on the water pan and bottom plate is cleaned up Passed Failed The air filter is correctly installed according to the airflow direction marked on the frame Passed Failed Condensate water in the water pan is drained smoothly Passed Failed All adjustable side panels have been installed Passed F...

Page 139: ...cooling product in the same network segment If the IP address of the smart cooling product is 192 168 xxx xxx subnet mask is 255 255 255 000 and default gateway is 192 168 xxx xxx set the PC IP address to 192 168 xxx xxx subnet mask to 255 255 255 000 and default gateway to 192 168 xxx xxx Log in from a WAN a Connect a network cable between the network port on the PC and the COM port on the smart ...

Page 140: ...roduct connects to the Internet and the PC in a LAN accesses the Internet over a proxy server do not perform Step 2 3 and Step 2 4 Otherwise you will fail to access the WebUI 1 Open the Internet Explorer and choose Tools Internet Options 2 Click the Advanced tab and select Use TLS1 1 and Use TLS1 2 Figure 7 1 Setting Internet options 3 Optional Click the Connections tab and select LAN settings 4 O...

Page 141: ...e NOTE If no certificate is installed a warning is displayed Click Continue to this website not recommended Figure 7 3 Security certificate problem 2 On the login page enter the preset user name admin and preset password Changeme set the language enter the verification code and click Log In FusionCol8000 E240 Modular Indirect Evaporative Cooling System User Manual 7 WebUI Issue 02 2021 04 15 Copyr...

Page 142: ...r example set the temperature and humidity of the smart cooling product enable the temperature and humidity sensor and set the fan control type Query Queries historical alarms System Settings Allows you to upload a network security certificate Allows you to set the time zone time and date Allows you to set the IP address Allows you to set Modbus communications parameters Allows you to set SNMP com...

Page 143: ...recautions and be able to correctly perform all operations During operation comply with the safety symbols on the device and all the safety instructions in this document The safety precautions provided in this document do not cover all the safety precautions Huawei shall not be liable for any consequence caused by the violation of the safety operation regulations and design production and usage st...

Page 144: ...ically isolated from the general power supply After installing the smart cooling product if the construction company is still in the process of construction take protective measures to prevent sundries and dust from falling into the smart cooling product It is recommended that the following maintenance items be performed every three to six months The actual maintenance period depends on the loads ...

Page 145: ...on the surface of the water tank filter Compresso r The compressor is secured Tighten screws if the compressor is not secured The operating compressor generates no metal friction noise or collision noise from inside Replace the compressor Pipe The refrigerant pipe does not leak or corrode and is properly wrapped with thermal insulation foam Repair the leakage points and rewrap thermal insulation f...

Page 146: ...n and exhaust fan are not loose or distorted Tighten the screws using a 10 socket wrench Water pump The water pump is not rusted Remove the rust No water leaks from the water pump spindle seal If water leaks replace the water pump or water pump spindle seal 8 2 2 Quarterly Maintenance Table 8 2 Quarterly maintenance checklist Comp onent Item on the Basis of Monthly Maintenance Troubleshooting Moni...

Page 147: ...ly maintenance checklist Compone nt Item on the Basis of Quarterly Maintenance Troubleshooting Sensor Use a precision T H sensor to calibrate the T H sensors inside and outside the device If the temperature deviation is greater than 1 C or humidity deviation is greater than 5 the T H sensor must be calibrated or replaced Welding point and needle valve Check that welding points and needle valves do...

Page 148: ... four years If the air is not completely exhausted air blockage may occur and the water pump cannot spray normally In this case you need to manually exhaust air When the water pump is running remove the exhaust plug on the smart cooling product When water flows out of the exhaust hole reinstall and tighten the exhaust plug 8 3 Troubleshooting Fan NOTICE If any of the following exceptions occurs wh...

Page 149: ...irculation is normal Clear foreign matters if necessary The fan blade is blocked or dirty Check the ambient temperature of the fan Check the voltage The fan blade is blocked or dirty Power off the motor and prevent it from being connected again Check whether the motor is powered off Clear foreign matters or contaminants The airflow direction is incorrect the direction of the motor is opposite to t...

Page 150: ...r the airflow is smooth intake exhaust air damper and air filter The concentricity of the air intake ring is incorrect applicable to a centrifugal fan Observe the installation precautions Electric Hazards Electrical components can only be operated by professional electricians or persons familiar with electricity or under the supervision of an electrician Comply with five electrical safety regulati...

Page 151: ...tection devices such as air circuit breakers and AC contactors to ensure their safety and reliability Smart Cooling Product Structure Apply lubricants to all locking fixtures for lubrication Repair the damaged parts to avoid corrosion Check the air tightness and connection Common Faults If an exception occurs during the running of the smart cooling product locate the fault immediately You can cont...

Page 152: ...ely small the air duct is excessively short Balance the air volume and air pressure The motor is burnt The motor is overloaded Balance the air volume and replace the motor The motor is poorly insulated Replace the motor The running sound is abnormal The compressor fan or pipes are loose Check and secure loose parts The air damper is shaking Adjust the air damper The compressor does not work The hi...

Page 153: ...rant is insufficient Charge more refrigerant The indoor temperature is set too low Modify the temperature setting The air filter is dirty or blocked Replace the air filter The external residual pressure is too high and airflow decreases Check whether the air channels are blocked The condensing pressure is too low Check the condenser The compressor generates a loud noise Liquid is returning to the ...

Page 154: ...st plug 8 4 Alarm Reference NOTICE If the Clear button is not displayed on the Details screen of an alarm the alarm can be automatically cleared Such an alarm can be automatically cleared after the fault is rectified If the Clear button is displayed on the Details screen of an alarm the alarm can be manually cleared Such an alarm is manually cleared by tapping the Clear button after the fault is r...

Page 155: ...air 1 temperature sensor fault Heat exchanger core exhaust air 2 temperature sensor fault L1 precooling module exhaust air 1 temp sensor fault L1 precooling module exhaust air 2 temp sensor fault L2 precooling module intake air 1 temp sensor fault L2 precooling module intake air 2 temp sensor fault Major The cables to the temperature sensor are loose or damaged The temperature sensor is faulty 1 C...

Page 156: ...s inappropriate The value detected by the temperature sensor or temperature and humidity sensor is different from the actual value 1 Adjust the positions of the temperature sensors or temperature and humidity sensors 2 Add air conditioners or contact Huawei technical support 3 Measure the ambient temperature Check whether other causes exist if the alarm persists in a long time after startup 4 Adju...

Page 157: ... is different from the actual value The air filters are blocked 1 Adjust the positions of the temperature sensors or temperature and humidity sensors 2 Contact Huawei technical support 3 Measure the ambient temperature Check whether other causes exist if the alarm persists in a long time after startup 4 Adjust the low temperature alarm threshold 5 Calibrate or replace the temperature sensor or tem...

Page 158: ...sensor comm failed Outdoor intake air 1 T H sensor comm fail Precooling module temp humid sensor comm failed Major The cables to the temperature and humidity sensor are loose or damaged The DIP switch of the temperature and humidity sensor is set incorrectly The temperature and humidity sensor is faulty The communications port of the main control board is faulty 1 Check the cables to the temperatu...

Page 159: ...e alarm threshold Maintain or replace the fan and clear the accumulated runtime A025 01 Return air filter blocked alarm Fresh air filter blocked alarm Outdoor intake air filter blocked alarm Warning Air filters are blocked or dirty The differential pressure switch is faulty An inappropriate threshold is set for the differential pressure switch The pressure tube of the differential pressure switch ...

Page 160: ... the liquid pipe temperature sensor are loose or damaged The liquid pipe temperature sensor is faulty 1 Check the cables to the liquid pipe temperature sensor 2 Maintain or replace the liquid pipe temperature sensor A042 01 Remote shutdown alarm Critical The remote shutdown dry contact is triggered The cables to the remote shutdown dry contact are loose or damaged 1 Check the status of the remote ...

Page 161: ...alve coil and cable connections are faulty The indoor fan is faulty The ambient temperature is below the lower threshold 1 Identify and repair the leaking point and refill refrigerant after maintenance 2 Maintain or replace the solenoid valve coil or the solenoid valve 3 Calibrate or replace the pressure sensor 4 Maintain or replace the filter dryer 5 Maintain or replace the expansion valve or the...

Page 162: ... sensor or temperature and humidity sensor is different from the actual value 1 Adjust the positions of the temperature sensors or temperature and humidity sensors 2 Add air conditioners or contact Huawei technical support 3 Measure the ambient temperature Check whether other causes exist if the alarm persists in a long time after startup 4 Adjust the high temperature alarm threshold 5 Calibrate o...

Page 163: ...sensor is different from the actual value The air filters are blocked 1 Adjust the positions of the temperature sensors or temperature and humidity sensors 2 Contact Huawei technical support 3 Measure the ambient temperature Check whether other causes exist if the alarm persists in a long time after startup 4 Adjust the low temperature alarm threshold 5 Calibrate or replace the temperature sensor ...

Page 164: ... sensor or temperature and humidity sensor is different from the actual value 1 Adjust the positions of the temperature sensors or temperature and humidity sensors 2 Add air conditioners or contact Huawei technical support 3 Measure the ambient temperature Check whether other causes exist if the alarm persists in a long time after startup 4 Adjust the high temperature alarm threshold 5 Calibrate o...

Page 165: ...r contact Huawei technical support 3 Measure the ambient temperature Check whether other causes exist if the alarm persists in a long time after startup 4 Adjust the high temperature alarm threshold 5 Calibrate or replace the temperature sensor or temperature and humidity sensor A055 01 Compressor 1 discharge temperature sensor fault Compressor 2 discharge temperature sensor fault Compressor 3 dis...

Page 166: ...r is faulty 1 Check the cables to the pressure sensor 2 Replace the pressure sensor A063 01 Compressor 1 drive communication failed alarm Compressor 2 drive communication failed alarm Compressor 3 drive communication failed alarm Major The cables to the compressor drive are loose or damaged The compressor drive is faulty 1 Check the cables to the compressor drive 2 Maintain or replace the compress...

Page 167: ...rom the fan replace the drive A077 20 Indoor fan 1 fault Indoor fan 2 fault Indoor fan 3 fault Indoor fan 4 fault Indoor fan 5 fault Exhaust fan 1 fault Exhaust fan 2 fault Exhaust fan 3 fault Exhaust fan 4 fault Major The ground cable to the fan is not connected properly The fan is faulty 1 Check the ground cable connection to the fan 2 Maintain or replace the fan A089 01 Compressor 1 drive speed...

Page 168: ...r temperature and humidity sensor is different from the actual value 1 Adjust the positions of the temperature sensors or temperature and humidity sensors 2 Contact Huawei technical support 3 Measure the ambient temperature Check whether other causes exist if the alarm persists in a long time after startup 4 Adjust the low temperature alarm threshold 5 Calibrate or replace the temperature sensor o...

Page 169: ... in a long time after startup 4 Adjust the low temperature alarm threshold 5 Calibrate or replace the temperature sensor or temperature and humidity sensor A093 01 High humidity alarm Warning The thermal load is low The ambient humidity exceeds the upper threshold The temperature and humidity sensor is not installed in a proper position The high humidity alarm threshold is inappropriate The value ...

Page 170: ...time of the fan exceeds the alarm threshold The cable to the fan is not connected properly The power supply to the fan is abnormal 1 Maintain or replace the fan and clear the accumulated runtime 2 Check the cable connection to the fan 3 Check the power supply to the fan A105 01 Exhaust fan function failure alarm Critical The fan is faulty The cable to the fan is not connected properly The power su...

Page 171: ...ture sensor fault Compressor 3 suction temperature sensor fault Paral comp sys suction temp sensor fault Major The cables to the suction temperature sensor are loose or damaged The suction temperature sensor is faulty 1 Check cables to the suction temperature sensor 2 Maintain or replace the suction temperature sensor A172 01 SPD and voltage detection board comm failed Backup SPD and volt detectio...

Page 172: ...wer failure 1 Start the equipment after preheating is complete or set the Compressor preheating parameter to Off to stop preheating 2 Wait until compressor preheating is complete or set the Compressor preheating parameter to Off to stop preheating A193 01 Air side diff pressure sensor fault Major The cable to the differential pressure sensor is loose or damaged The pressure tube of the differentia...

Page 173: ...l wizard startup is complete or clear the alarm manually to exit wizard startup A222 01 Main control module power supply abnormal Major The system is powered off The main control module is in poor contact The auxiliary power supply is faulty The auxiliary power supply is in poor contact The main control module is faulty 1 Power on the system 2 Check the interconnection module in the main control m...

Page 174: ...y abnormal Indoor fan 2 power supply abnormal Indoor fan 3 power supply abnormal Indoor fan 4 power supply abnormal Indoor fan 5 power supply abnormal Exhaust fan 1 power supply abnormal Exhaust fan 2 power supply abnormal Exhaust fan 3 power supply abnormal Exhaust fan 4 power supply abnormal Major The cable to the fan is not connected properly The fan drive is faulty 1 Check the cable connection...

Page 175: ...ing abnormal alarm Major Any two units in the teamwork group have the same address The software versions of the air conditioners in the group are inconsistent The sensor that corresponds to the temperature and humidity control type for the master unit is not enabled on this air conditioner 1 Change the addresses of the units 2 Upgrade the air conditioner software For details see the section about ...

Page 176: ...ndoor fan are loose or damaged All sensors for controlling the indoor fan are faulty 1 Enable the sensors for controlling the indoor fan 2 Check the cable connections to the sensors for controlling the indoor fan 3 Maintain or replace the sensors for controlling the indoor fan A279 01 A279 04 Supply air damper fault Return air damper fault Exhaust air damper fault Critical The control cable to the...

Page 177: ...e 3 temp humid sensor fault Hot aisle 4 temp humid sensor fault Hot aisle 5 temp humid sensor fault Hot aisle 6 T H sensor fault Outdoor intake air 1 T H sensor fault Outdoor intake air 3 temperature invalid Major The cables to the temperature and humidity sensor are loose or damaged The temperature and humidity sensor is faulty 1 Check the cables to the temperature and humidity sensor 2 Maintain ...

Page 178: ...281 08 A281 10 Power voltage abnormal Backup power voltage abnormal Auxiliary cooling power voltage abnormal Auxiliary cooling backup power voltage abnormal Major The power supply voltage is below the lower threshold The cables to the SPD and voltage detection board are loose or damaged The SPD and voltage detection board is faulty 1 Check that the power supply voltage is within the operating rang...

Page 179: ...se sequence abnormal Major The power grid is unstable The phase A input cable is faulty 1 Check the power grid 2 Rectify the fault of the phase A input cable A282 08 Power phase sequence abnormal Critical The power grid is unstable The phase B input cable is faulty 1 Check the power grid 2 Rectify the fault of the phase B input cable A282 08 Backup power phase sequence abnormal Auxiliary cooling p...

Page 180: ...al Auxiliary cooling backup power phase sequence abnormal Major The power grid is unstable The phase C input cable is faulty 1 Check the power grid 2 Rectify the fault of the phase C input cable FusionCol8000 E240 Modular Indirect Evaporative Cooling System User Manual 8 System Maintenance Issue 02 2021 04 15 Copyright Huawei Technologies Co Ltd 171 ...

Page 181: ... too high The water supply for the water cooled module is insufficient The inside of the water cooled module is dirty or blocked The water valve of the water cooled module is faulty 1 Identify and repair the leaking point and refill refrigerant after maintenance 2 Clean the condenser fins 3 Measure the ambient temperature 4 Calibrate or replace the temperature sensor 5 Check the input power of the...

Page 182: ...is too high The water supply for the water cooled module is insufficient The inside of the water cooled module is dirty or blocked The water valve of the water cooled module is faulty 1 Identify and repair the leaking point and refill refrigerant after maintenance 2 Clean the condenser fins 3 Measure the ambient temperature 4 Calibrate or replace the temperature sensor 5 Check the input power of t...

Page 183: ... module is insufficient The inside of the water cooled module is dirty or blocked The water valve of the water cooled module is faulty 1 Check the input power of the outdoor unit 2 Check the cables to the indoor and outdoor fans 3 Clean the condenser fins 4 Maintain or replace the outdoor fan or its drive 5 Calibrate or replace the pressure sensor 6 Decrease certain amount of refrigerant 7 Maintai...

Page 184: ...high The water supply for the water cooled module is insufficient The inside of the water cooled module is dirty or blocked The water valve of the water cooled module is faulty 1 Check the input power of the outdoor unit 2 Check the cables to the indoor and outdoor fans 3 Clean the condenser fins 4 Maintain or replace the outdoor fan or its drive 5 Calibrate or replace the pressure sensor 6 Decrea...

Page 185: ... high The water supply for the water cooled module is insufficient The inside of the water cooled module is dirty or blocked The water valve of the water cooled module is faulty 1 Check the input power of the outdoor unit 2 Check the cables to the indoor and outdoor fans 3 Clean the condenser fins 4 Maintain or replace the outdoor fan or its drive 5 Calibrate or replace the pressure sensor 6 Decre...

Page 186: ... are faulty The indoor fan is faulty The ambient temperature is below the lower threshold 1 Identify and repair the leaking point and refill refrigerant after maintenance 2 Maintain or replace the solenoid valve coil or the solenoid valve 3 Calibrate or replace the pressure sensor 4 Maintain or replace the filter dryer 5 Maintain or replace the expansion valve or the coil and reconnect cables 6 Ma...

Page 187: ...ter dryer 5 Maintain or replace the expansion valve or the coil and reconnect cables 6 Maintain or replace the indoor fan 7 Measure the ambient temperature A28E 01 Compressor 1 drive alarm Compressor 2 drive alarm Compressor 3 drive alarm Major The compressor drive is faulty The compressor is faulty 1 Maintain or replace the compressor drive 2 Maintain or replace the compressor A28E 02 Compressor ...

Page 188: ...pressor 1 drive power supply abnormal Compressor 2 drive power supply abnormal Compressor 3 drive power supply abnormal Major The power supply voltage is low The compressor drive is faulty The primary power supply is faulty or the cables to the compressor drive are loose or damaged 1 Check the power supply voltage 2 Maintain or replace the compressor drive 3 Check the primary power supply or the c...

Page 189: ...mpressor 1 drive power supply abnormal Compressor 2 drive power supply abnormal Compressor 3 drive power supply abnormal Major The cables to phase W of the compressor drive are loose or damaged The compressor drive is faulty 1 Check the power supply voltage 2 Maintain or replace the compressor drive A291 01 A291 02 Compressor 1 overcurrent alarm Compressor 2 overcurrent alarm Compressor 3 overcurr...

Page 190: ... 5 Maintain or replace the dehumidification solenoid valve coil A296 02 EEV 1 low superheat degree alarm EEV 2 low superheat degree alarm Critical The EEV coil is loose The EEV coil is faulty The EEV is faulty The cables to the EEV coil are loose or damaged 1 Reinstall the EEV coil 2 Replace the EEV coil 3 Replace the EEV 4 Check and maintain the cables to the EEV coil A296 02 Paral comp sys low s...

Page 191: ...pe 2 Check the cable connection to the spray drain valve 3 Replace the spray drain valve 4 Maintain the low spray float 5 Check the cable connection to the low spray float A305 01 Spray water supply abnormal Major The spray water supply is insufficient The low spray float does not float because the float is faulty The cable to the low spray float is not connected properly The cable to the spray wa...

Page 192: ...witch 6 Maintain the spray water flow switch 7 Maintain the low spray float A307 01 Spray water pump 1 exceed runtime alarm Warning The accumulated runtime the spray pump exceeds the alarm threshold Replace the pump and clear the accumulated runtime A308 01 Spray water pump 2 exceed runtime alarm Warning The accumulated runtime the spray pump exceeds the alarm threshold Replace the pump and clear ...

Page 193: ...ommunication failure Major The differential pressure sensor cable is loose or damaged The DIP switch of the differential pressure sensor is set incorrectly The differential pressure sensor is faulty The communications port of the main control board is faulty 1 Check the cable connection to the differential pressure sensor 2 Set the DIP switch of the differential pressure sensor correctly 3 Maintai...

Page 194: ... to the spray pump drive are loose or damaged The spray pump is faulty The spray pump drive is faulty 1 Check the output cables to the spray pump drive 2 Maintain or replace the spray pump 3 Maintain or replace the spray pump drive A364 01 Spray pump 1 drive overcurrent Spray pump 2 drive overcurrent Major The spray pump is faulty The spray pump drive is faulty 1 Maintain or replace the spray pump...

Page 195: ...r temperature and humidity sensor is different from the actual value The value detected by the precooling module temperature sensor is different from the actual value 1 Maintain the heat exchanger core 2 Maintain or replace the precooling module 3 Maintain the spray related parts 4 Maintain or replace the air filter 5 Calibrate or replace the temperature sensor or temperature and humidity sensor 6...

Page 196: ...Compressor drive 10 Liquid level sensor 11 Fan drive NOTE When replacing components you need to remove the corresponding adjustable side panel in the FDC scenario or open the corresponding maintenance door in the building scenario The following describes how to remove the corresponding adjustable side panel FusionCol8000 E240 Modular Indirect Evaporative Cooling System User Manual 8 System Mainten...

Page 197: ...ctional When replacing an air filter you need to use a maintenance platform For details how to prepare the platform see F Air filter Maintenance Platform Procedure Step 1 On the home screen of the display module tap Shutdown and turn off the device switch in the PDF NOTICE Exercise caution because the device is still energized after it is shut down on the screen of the display module Step 2 Replac...

Page 198: ...4 Replacing an air filter Step 4 Replace the indoor return air filter top Open the maintenance door corresponding to the air filter remove the fastener from the air filter and pull out the air filter FusionCol8000 E240 Modular Indirect Evaporative Cooling System User Manual 8 System Maintenance Issue 02 2021 04 15 Copyright Huawei Technologies Co Ltd 189 ...

Page 199: ... An air filter needs to be replaced A spare air filter of the same model is available and functional When replacing an air filter you need to use a maintenance platform For details how to prepare the platform see F Air filter Maintenance Platform Procedure Step 1 On the home screen of the display module tap Shutdown and turn off the device switch in the PDF NOTICE Exercise caution because the devi...

Page 200: ...ove the adjustable side panel corresponding to the air filter remove the fastener from the air filter and pull out the air filter Figure 8 7 Replacing an air filter Step 4 Install a new air filter and secure it Step 5 Install the air filter fasteners FusionCol8000 E240 Modular Indirect Evaporative Cooling System User Manual 8 System Maintenance Issue 02 2021 04 15 Copyright Huawei Technologies Co ...

Page 201: ...ential pressure switch can be maintained from the end only after the air filter is removed Procedure Step 1 On the home screen of the display module tap Shutdown and turn off the device switch in the PDF NOTICE Exercise caution because the device is still energized after it is shut down on the screen of the display module Step 2 Remove the outdoor intake air filter Step 3 Cut off the cable ties on...

Page 202: ...evice is running properly without generating alarms End 8 5 6 Replacing a Differential Pressure Switch FDC Scenario Prerequisites A differential pressure switch needs to be replaced A spare differential pressure switch of the same model is available and functional Tool Phillips screwdriver Context The differential pressure switch can be maintained from the end only after the air filter is removed ...

Page 203: ...illips screwdriver and remove the differential pressure switch Figure 8 10 Removing the differential pressure switch Step 7 Set a new value for the differential pressure switch based on the nearby label Step 8 Install the new differential pressure switch install the pressure inlet tube and connect cables Step 9 Power on the device and tap Start on the home screen Ensure that the device is running ...

Page 204: ... still energized after it is shut down on the screen of the display module Step 2 Remove the indoor return air filter Step 3 Remove the indoor return air T H sensor Cut off the cable tie that secures the cable and remove the cable from the T H sensor Figure 8 11 Removing a T H sensor Step 4 Remove the outdoor intake air T H sensor Remove the screws from the sheet metal fastener of the T H sensor F...

Page 205: ... Start on the home screen Ensure that the device is running properly without generating alarms End 8 5 8 Replacing a T H Sensor FDC Scenario Prerequisites A T H sensor needs to be replaced A spare T H sensor of the same model is available and functional Tools Phillips screwdriver scissors Procedure Step 1 On the home screen of the display module tap Shutdown and turn off the device switch in the P...

Page 206: ...rom the sheet metal fastener of the T H sensor push the baffle plate and remove the T H sensor and the sheet metal fastener Figure 8 13 Removing the T H sensor sheet metal Figure 8 14 Removing a T H sensor Step 4 Remove the outdoor intake air T H sensor Remove the screws from the sheet metal fastener of the T H sensor FusionCol8000 E240 Modular Indirect Evaporative Cooling System User Manual 8 Sys...

Page 207: ...Step 8 Power on the device and tap Start on the home screen Ensure that the device is running properly without generating alarms End 8 5 9 Replacing an Air Exhaust NTC Temperature Sensor Building Scenario Prerequisites An NTC temperature sensor needs to be replaced A spare NTC temperature sensor of the same model is available and functional Tool Phillips screwdriver FusionCol8000 E240 Modular Indi...

Page 208: ...able ties and remove the screws that secure the NTC temperature sensor Step 5 Remove the interconnection terminal from the cable of the NTC temperature sensor Step 6 Install the new NTC temperature sensor reconnect the cables and secure the NTC temperature sensor in the original position Step 7 Bind the cable ties Step 8 Power on the device and tap Start on the home screen Ensure that the device i...

Page 209: ...minal from the cable of the NTC temperature sensor Step 5 Install the new NTC temperature sensor reconnect the cables and secure the NTC temperature sensor in the original position Step 6 Bind the cable ties Step 7 Power on the device and tap Start on the home screen Ensure that the device is running properly without generating alarms End 8 5 11 Replacing an Air Supply NTC Temperature Sensor Prere...

Page 210: ... reconnect the cables and secure the NTC temperature sensor in the original position Step 7 Power on the device and tap Start on the home screen Ensure that the device is running properly without generating alarms End 8 5 12 Replacing an Air Supply Fan Prerequisites A fan needs to be replaced A spare fan of the same model is available and functional Tools protection gloves Phillips screwdriver dia...

Page 211: ...be replaced Building scenario Remove the maintenance door frame post and water pipe in front of the fan FDC scenario Remove the adjustable side panel post and water pipe Figure 8 18 Removing the maintenance door frame building scenario Figure 8 19 Removing the post and water pipe 1 Post 2 Water pipe Step 4 Remove the sheet metal FusionCol8000 E240 Modular Indirect Evaporative Cooling System User M...

Page 212: ...sons are required to pull out the fan If only the first fan needs to be replaced pull out the two fans remove the bolts between the first and second fans and replace the first fan When you pull out the second fan horizontally the latch is stuck Press the latch and pull out the fan horizontally Step 7 Unscrew the fan support and take out the fan FusionCol8000 E240 Modular Indirect Evaporative Cooli...

Page 213: ...terminal using cable ties Step 10 Install the adjustable side panel Step 11 Power on the smart cooling product choose Maint Startup Wizard on the home screen and commission the indoor fan to check that it works properly before you exit Step 12 Choose Maint Performance Maint on the home screen and clear the total runtime of the indoor fan FusionCol8000 E240 Modular Indirect Evaporative Cooling Syst...

Page 214: ...OTICE Exercise caution because the device is still energized after it is shut down on the screen of the display module Step 2 Remove the adjustable side panel and beam from the fan to be maintained NOTE When maintaining the fan stand on the operation platform Step 3 Remove the side sealing plate from the fan to be maintained Step 4 Cut the cable tie that binds the cable connected to the faulty fan...

Page 215: ...nd second fans and replace the first fan When you pull out the second fan horizontally the latch is stuck Press the latch and pull out the fan horizontally Step 6 Unscrew the fan support and take out the fan Figure 8 25 Removing a fan FusionCol8000 E240 Modular Indirect Evaporative Cooling System User Manual 8 System Maintenance Issue 02 2021 04 15 Copyright Huawei Technologies Co Ltd 206 ...

Page 216: ... home screen and clear the total runtime of the exhaust fan Step 12 Tap Startup on the home screen Ensure that the device is running normally without any alarms End 8 5 14 Replacing a Precooling Module Prerequisites A precooling module needs to be replaced A spare precooling module of the same model is available and functional Tools protective gloves Phillips screwdriver Procedure Step 1 On the co...

Page 217: ...ng a precooling module Step 5 Install the new precooling module and secure the sheet metal Step 6 Install the adjustable side panel and beam Step 7 Tap Start on the home screen Ensure that the device is running normally without any alarms End 8 5 15 Replacing a Compressor 8 5 15 1 Replacing a Compressor FusionCol8000 E240 Modular Indirect Evaporative Cooling System User Manual 8 System Maintenance...

Page 218: ...ssor immediately after you remove the rubber plugs of suction inlet and discharge outlet to prevent the moisture intake Procedure Step 1 On the home screen of the display module tap Shutdown and turn off the device switch in the PDF NOTICE Exercise caution because the device is still energized after it is shut down on the screen of the display module Step 2 Remove the adjustable side panels for th...

Page 219: ...water from entering 2 Use a 13 socket wrench or solid wrench to remove the four nut washers and spring washers that secure the compressor and remove the compressor NOTICE Do not hold the suction inlet and exhaust outlet to move the compressor Figure 8 29 Removing a compressor FusionCol8000 E240 Modular Indirect Evaporative Cooling System User Manual 8 System Maintenance Issue 02 2021 04 15 Copyrig...

Page 220: ...t with nitrogen Step 11 After checking that the smart cooling product does not leak vacuumize the smart cooling product and fill the refrigerant Step 12 Check that the compressor cable phase sequence is correct power on the device and tap Start on the home screen Step 13 Choose Maint Diagnostic Enter to check the system pressure and temperature and ensure the refrigerant is charged with an optimal...

Page 221: ...igerant does not meet the requirements and needs to be replaced Figure 8 30 Refrigerant detection Table 8 6 Mapping between temperatures and R410A saturation pressures Temperatur e ºC Saturation Pressure Gauge Pressure MPa Temperatu re ºC Saturation Pressure Gauge Pressure MPa Temperatu re ºC Saturatio n Pressure Gauge Pressure MPa 0 0 7 19 1 31 38 2 21 1 0 73 20 1 35 39 2 27 2 0 75 21 1 39 40 2 3...

Page 222: ... at least 4 0 MPa and the rubber hose must withstand a pressure of at least 4 5 MPa Only nitrogen can be used for pressure preservation and leakage detection During pressure preservation do not remove the rubber hoses and pressure gauges otherwise nitrogen may leak When the outdoor unit is connected to an air cooled outdoor unit or water cooled module the nitrogen injection and pressure preservati...

Page 223: ...change perform the test again NOTICE The outlet pressure of the reducing valve should be within 3 0 MPa otherwise components may be damaged Step 3 If the pressure decreases apply soapy water or use a halogen leak detector to check for any leakage If the pressure is stable expel the nitrogen End 8 5 15 4 Vacuumizing and Precharging Refrigerant CAUTION During the commissioning of the smart cooling p...

Page 224: ...ystem is thoroughly vacummized Procedure Step 1 Connect the pressure gauge and vacuum pump to vacuumize the device Figure 8 32 Vacuumizing 1 Vacuum pump 2 Pressure gauge 3 Low pressure needle valve 4 Liquid pipe needle valve 5 Sight glass Step 2 In the beginning the vacuum pump makes loud noises and exhausts white smoke from the exhaust vent After 10 minutes if it still exhausts white smoke observ...

Page 225: ...ceed 90 Pa absolute pressure NOTE If the minimum reading of the pressure gauge is greater than 60 Pa absolute pressure ensure that the pointer stays at the smallest scale of the pressure gauge in vacuumizing and preserve the pressure for 1 hour Then check that the pressure does not rise evidently End 8 5 15 4 3 Precharging Refrigerant Prerequisites Before charging refrigerant ensure that air is ex...

Page 226: ...refrigerant These measures ensure that the refrigerant is charged in the liquid state Step 4 Open the low pressure gauge valve Charge 1 kg of refrigerant from the low pressure side and then close the low pressure gauge valve Then open the high pressure gauge valve and charge the remaining refrigerant from the liquid pipe needle valve NOTICE Do not move the hose or refrigerant cylinder when chargin...

Page 227: ...e the device may be damaged Procedure Step 1 Tap Start on the home screen Step 2 Choose Maint Diagnostic Enter to enter the diagnostic mode Step 3 Change the compressor rotational speed to 3000 rpm Step 4 Open the low pressure valve of the pressure gauge and charge the remaining refrigerant from the low pressure needle valve in small flow or intermittently Figure 8 34 Charging the remaining refrig...

Page 228: ...gerant is underfilled the suction and discharge pressures are low and the suction superheat degree is high 2 The air intake and exhaust vents of the unit are not blocked If the air intake vent and air exhaust vent are blocked the discharge pressure will be high Step 6 After charging refrigerant close all valves Step 7 Tap to exit the diagnostic mode Step 8 Tap Shutdown on the home screen End 8 5 1...

Page 229: ...e refrigerant from the low pressure needle valve and liquid pipe needle valve to ensure that there is no pressure inside the system Step 3 Remove the filter dryer NOTICE During welding use a silver copper welding rod containing 5 silver Check that the welding joints are in good condition without poor welding To avoid burning the internal components other pipes thermal insulation foam power cables ...

Page 230: ... leakage test with nitrogen Step 6 After checking that the smart cooling product does not leak vacuumize the smart cooling product and fill the refrigerant Step 7 Power on the device and tap Start on the home screen Ensure that the smart cooling product is running normally without any alarms End 8 5 17 Replacing a Compressor Drive Prerequisites A drive needs to be replaced A spare drive of the sam...

Page 231: ...le side panels for the compressor drive Step 3 Remove all cables from the drive and cut the cable ties using diagonal pliers Step 4 Remove the four screws on the drive using a Phillips screwdriver and pull out the drive Figure 8 37 Removing a drive Step 5 Install the new drive Step 6 Connect the cables to the drive Step 7 Install the adjustable side panels Step 8 Power on the smart cooling product...

Page 232: ...for 10 minutes Otherwise electric shocks may occur Procedure Step 1 On the home screen of the display module tap Shutdown and turn off the device switch in the PDF NOTICE Exercise caution because the device is still energized after it is shut down on the screen of the display module Step 2 Remove the adjustable side panel Step 3 Flip the clip on the fan drive to be replaced Step 4 Pull out the han...

Page 233: ...End 8 5 19 Replacing a Liquid Level Sensor Prerequisites A liquid level sensor needs to be replaced A spare liquid level sensor of the same model is available and functional Tool solid wrench Context The liquid level sensor can be maintained only at the water tank Procedure Step 1 On the home screen of the display module tap Shutdown and turn off the device switch in the PDF NOTICE Exercise cautio...

Page 234: ...Step 4 Replace the liquid level sensor at the bottom of the precooling module Remove the adjustable side panel and water barrier of the air supply fan Cut off the cable tie that secures the liquid level sensor cable and remove the interconnection terminal Remove the fastener from the liquid level sensor at the bottom of the precooling module Loosen the nut on the liquid level sensor using a wrench...

Page 235: ...acing a Water Pump Prerequisites A water pump needs to be replaced A spare water pump of the same model is available and functional Tools flat head screwdriver Phillips screwdriver socket wrench NOTICE Before replacing the water pump drain water from the water tank completely Procedure Step 1 On the home screen of the display module tap Shutdown and turn off the device switch in the PDF NOTICE Exe...

Page 236: ...the adjustable side panels Step 6 Power on the device choose Maint Performance Maint on the home screen of the display module to access the performance maintenance screen and clear the total runtime of the spray pump Step 7 Tap Start on the home screen Ensure that the device is running normally without any alarms End 8 5 21 Replacing a Switch Prerequisites A switch needs to be replaced A spare swi...

Page 237: ...ver and pull the switch outwards to remove it Figure 8 43 Replacing a switch NOTICE The figure is for reference only The actual product may vary Step 5 Install the new switch Clamp the clip at the lower side of the new switch to the guide rail push the switch upwards and press the switch inwards Step 6 Connect the cables again Step 7 Close the door of the electric control box Step 8 Power on the d...

Page 238: ...n of the display module Step 3 Press the snap ring of the faulty contactor using a flat head screwdriver and pull the contactor outwards to remove it Figure 8 44 Removing a contactor NOTICE The figure is for reference only The actual product may vary Step 4 Install the new contactor Clamp the clip at the lower side of the new contactor to the guide rail push the contactor upwards and press the con...

Page 239: ... box Step 2 On the home screen of the display module tap Shutdown and turn off the device switch in the PDF NOTICE Exercise caution because the device is still energized after it is shut down on the home screen of the display module Step 3 Pry the clip ring of the faulty SPD using a flat head screwdriver and remove the faulty SPD Figure 8 45 Removing an SPD NOTICE The figure is for reference only ...

Page 240: ...ch in the PDF NOTICE Exercise caution because the device is still energized after it is shut down on the home screen of the display module Step 3 Locate the fuse to be replaced open the blade fuse holder and remove the faulty fuse using a flat head screwdriver Step 4 Install the new fuse and close the fuse holder Step 5 Close the door of the electric control box Step 6 Power on the device and tap ...

Page 241: ... out the coil Step 5 Remove the base Remove the coil press the clip on the faulty base using a flat head screwdriver and pull the base outwards to remove it Figure 8 46 Replacing a relay 1 Base 2 Coil 3 Clip ring 4 Metal plate Step 6 Install a new coil or base Step 7 Close the door of the electric control box Step 8 Power on the device and tap Start on the home screen Ensure that the device is run...

Page 242: ...rves show the recent temperature and humidify changes You can choose to display the curves in recent one hour one day seven days or 30 days Procedure Step 1 Tap T H Curve on the home screen Figure 9 1 T H Curve screen FusionCol8000 E240 Modular Indirect Evaporative Cooling System User Manual 9 FAQ Issue 02 2021 04 15 Copyright Huawei Technologies Co Ltd 233 ...

Page 243: ...9 1 2 How Do I View Logs Context The Query Logs screen displays the operations performed by the user Procedure Step 1 Choose Maint Query Logs on the home screen End 9 1 3 How Do I View Component Status Context You can view the component status on the display module in the following two ways You can query the status of important components such as the compressor and indoor fan on the Status Summary...

Page 244: ...ol board compressor SPD voltage detection board and exhaust fan When the cold and hot aisles T H boards are enabled the information about the corresponding cold and hot aisles is displayed on the T H Board under About Version Info or T H Board under About E label When the cold and hot aisles T H boards are disabled the information about the corresponding cold and hot aisles is not displayed on the...

Page 245: ...in the status bar tap Off The icon changes to End 9 1 9 How Do I Handle Alarms Procedure Step 1 Tap or choose Alarms Query Act Alarms on the home screen to enter the active alarm screen Figure 9 3 Active alarms NOTE Active alarms are sorted by the generating time in descending order If active alarms exist they are displayed on the alarm bar in turn You can query an alarm on the alarm list in Alarm...

Page 246: ...smart cooling products Perform operations as required Step 3 Tap Fault Diagnosis_Repair to view the diagnosis report Rectify the faults by following instructions in the diagnosis report Figure 9 5 Diagnosis report End Follow up Procedure To query historical alarms choose Common Function Query Hist Alarms on the home screen or choose Alarms Query Hist Alarms on the home screen NOTE Historical alarm...

Page 247: ...eturn air detection point is 20 C while the sensor measured 22 C the sensor has an error of 2 C and the calibration value can be set to 2 C Procedure Step 1 Choose Maint Sensor Calibration on the home screen Step 2 Fill the calibration value based on the measured error End 9 1 12 How Do I Check the Display of Normal Air Volume Prerequisites Tool differential pressure gauge purchased onsite Procedu...

Page 248: ...late of the fan for about 30 mm Step 4 Insert the positive pressure tube of the differential pressure gauge into the unit through the cable hole for about 30 mm Figure 9 7 Pressure measurement points 1 Pressure measurement point for the negative pressure tube 2 Pressure measurement point for the positive pressure tube NOTE The cross section of the pressure tubes must be perpendicular to the wind d...

Page 249: ... parameters Confirm with Huawei technical support before modifying parameters which cannot be modified by user operator Otherwise Huawei will not be liable for any consequences of the modification performed by the user Only certified professionals are allowed to modify advanced parameters of smart cooling products Unauthorized modifications can result in smart cooling product malfunction and even ...

Page 250: ... display a message indicating that the password complexity is low and asking you to set a new one Examples of low complexity passwords H uawei123 Password and openasadminAdmin23 Step 2 Tap Password to access the password change screen and change the password End 9 1 15 How Do I Set the Balance of Water and Electricity Consumption Procedure Step 1 On the home screen choose Settings System Settings ...

Page 251: ...threshold Standby power overfrequency alarm threshold Supply air high temperature alarm threshold 5 C Return air high temperature alarm threshold Supply air high temperature alarm threshold 5 C Hot aisle high temperature alarm threshold Cold aisle high temperature alarm threshold 5 C Hot aisle high temperature alarm threshold Cold aisle high temperature alarm threshold 5 C Return air high temperat...

Page 252: ... Component Context On the Diagnostic screen you can enable or disable components and control their output ratio To perform manual operations on system components in diagnostic mode ensure that the system is powered on The following describes how to commission an indoor fan Procedure Step 1 On the home screen choose Maint Diagnostic Enter to enter the diagnostic mode FusionCol8000 E240 Modular Indi...

Page 253: ... the minimum rotational speed Step 3 Check that the indoor fan works properly and no alarm is generated Step 4 Choose Maint Diagnostic Exit or tap to exit the diagnosis mode End 9 1 18 How Do I Query the Setting of a Parameter Before Change On the home screen choose Maint Query Logs to query the setting of a parameter before change The value before is the setting before change and the value after ...

Page 254: ...ons Export to enter the Select Path screen Figure 9 13 Select Path screen Step 2 On the Select Path screen specify the save path and tap Next In the displayed dialog box tap Yes Step 3 After the data is successfully exported tap Finish Step 4 On the home screen choose Maint USB Operations Remove USB to remove the USB flash drive in safe mode End 9 1 20 How Do I Export or Import a Configuration Fil...

Page 255: ...ialog box tap Yes Step 3 After the data is successfully exported tap Finish Step 4 On the home screen choose Maint USB Operations Remove USB to remove the USB flash drive in safe mode Step 5 On the home screen of smart cooling product 2 choose Maint USB Operations Import Config Figure 9 15 Selecting the configuration file Step 6 Select the file package to be imported and tap Next Figure 9 16 Confi...

Page 256: ...You are advised to use the FAT32 USB flash drive with a capacity less than or equal to 64 GB For a non FAT32 USB flash drive format it to the FAT32 format using a computer NOTICE Ensure that the key file has been encrypted using AES128 Before using a USB flash drive ensure that its data has been scanned by antivirus software and is secure Procedure Step 1 On the home screen choose Maint USB Operat...

Page 257: ... admin and password is Changeme by default The administrator has all rights including the rights for user management browsing and modifying parameters software upgrade and data import and export Operator The user name is operator and password is Changeme by default Operator has no rights for network security certification Modbus SNMP software upgrade and fault information Procedure Step 1 Change t...

Page 258: ...ncurrent online users End 9 2 2 How Do I Install a Network Security Certificate Context You have copied a network security certificate and its key you obtained to the PC Install a network security certificate if a security certificate problem message is displayed when you attempt to log in to the WebUI You need to apply to an organization authorized by the customer for a network security certifica...

Page 259: ...ils in the Alarm Description area to view alarm details of devices Step 3 To view historical alarms choose Query Historical Alarm set Equipment Start time End time and Sorting Mode and click Query End 9 2 4 How Do I Export or Import a Configuration File Context You can export parameter configurations for smart cooling product 1 to a PC If smart cooling product 2 needs the same parameter configurat...

Page 260: ...r an encryption password NOTICE If Encryption Password for Export is selected the exported data package will be encrypted and you need to enter the encryption password to decompress the data package To ensure data security you are advised to select Encryption Password for Export NOTE Record the password for decompressing the data package Step 4 Click Export Fault Information Step 5 Save the export...

Page 261: ... Do you want to change the IP address dialog box click OK End 9 2 7 How Do I View Version Information Procedure Step 1 Log in to the WebUI as an administrator Step 2 Click in the upper right corner of the home page and view the version information Step 3 Choose Maintenance Version Information and view the version information software version and BSP version End FusionCol8000 E240 Modular Indirect ...

Page 262: ...the device 3 Clean visible rubbish and dust inside the device Step 2 Clean the exterior 1 Clear dust rain marks or stains on the device exterior using a long handled soft brush dipped with alkaline or neutral detergent 2 Wash the device exterior with clean water NOTE It is recommended that you clean the device once every quarter End FusionCol8000 E240 Modular Indirect Evaporative Cooling System Us...

Page 263: ...d area and its surrounding The paint should also be free from bulges scratches flake off or cracks Ensure that the outdoor area without shelters is not subject to bad weather conditions such as raining sandstorm strong wind or snowing during paint repair Ensure that the required paint has been prepared based on the color palette delivered with the product The color palette is used only for the cab...

Page 264: ...e paint coating should be thin and even Paint drops are prohibited on the coating The surface should be smooth 5 Leave the repainted area for about 60 minutes before performing any further operation Smudges and rust that cannot be wiped off Deep scratch primer damaged steel base material exposed Spray paint or paint zinc rich primer brush required for repainting a small area fine sandpaper anhydro...

Page 265: ... Procedure Step 1 Gently polish the damaged areas using fine sandpaper minimum grit size 180 to remove smudges or rust Figure B 1 Polishing a damaged area using sandpaper Step 2 Dip a piece of cotton cloth into anhydrous alcohol and wipe the polished or damaged area to remove the dirt and dust Then wipe off the alcohol with a clean and dry cotton cloth Figure B 2 Wiping a polished or damaged area ...

Page 266: ...the paint using a spray bottle brush or painting gun NOTE When a pattern has different colors to prevent undamaged areas and those with different colors from being polluted during repainting cover such areas using white paper and adhesive tape before repairing paint Figure B 4 Manual paint spray FusionCol8000 E240 Modular Indirect Evaporative Cooling System User Manual B Repairing Paint Issue 02 2...

Page 267: ...ing a painting gun End Follow up Procedure Check whether the surface meets the requirement after repainting FusionCol8000 E240 Modular Indirect Evaporative Cooling System User Manual B Repairing Paint Issue 02 2021 04 15 Copyright Huawei Technologies Co Ltd 258 ...

Page 268: ...ssword complexity check Checks password complexity Password Changes the password of the current login user LCD backlight Off delay Specifies the time of no operation after which the display module backlight turns off Key lifecycle Specifies the key lifecycle Settings Comm Settings WAN IP Settings For details see the section Setting Communications Parameters Settings Comm Settings LAN IP Settings F...

Page 269: ...ork when connecting to the WiFi of the smart cooling product Settings Comm Settings Modbus Settings Baud rate Set the baud rate as required The value should be consistent with that set on the NMS Communicat ion address Enter the communications address of the smart cooling product as planned The NMS communicates with the smart cooling product using this address and the communications addresses of t...

Page 270: ... on the site requirements NMS IP address Enter the actual IP address of the NMS IP addresses of the display panel client NMS and server NMS must be unique This parameter is configurable when Link mode is set to Client NMS port number It is recommended that you retain the default value If you need to change the value enter a value as required This parameter is configurable when Link mode is set to ...

Page 271: ...ystem generates an alarm Return air high temperature alarm When detecting that the alarm value is greater than the threshold the system generates an alarm Return air low temperature alarm When detecting that the alarm value is greater than the threshold the system generates an alarm Cold aisle high temperature alarm When detecting that the alarm value is greater than the threshold the system gener...

Page 272: ...PD and voltage detection board comm failed Enable Alarms are reported to the NMS Active alarms are displayed on the display module and the system performs related protection actions Disable No alarms are generated and no protection actions are performed Backup power failure alarm Enable Alarms are reported to the NMS Active alarms are displayed on the display module and the system performs related...

Page 273: ...erformed Settings System Settings Common Settings Temperature and humidity control type This parameter can be set to Cold aisle Hot aisle Return air or Supply air based on site requirements The temperature and humidity setpoints corresponding to the selected control mode are enabled Temperature setpoint After Temperature and humidity control type and the temperature value under this type are set t...

Page 274: ...al alarm Major alarm Alarm or Startup status based on the actual situation DO_2 Set this parameter to Smoke Water only Critical alarm Major alarm Alarm or Startup status based on the actual situation Settings System Settings System Control System start interval Specifies the time interval between the starts of units in a teamwork group Require password to start or shutdown onsite Set this paramete...

Page 275: ...sed on the actual situation DO_2 Set this parameter to Smoke Water only Critical alarm Major alarm Alarm or Startup status based on the actual situation Floor water overflow alarm action Shutdown Inactivity Only indoor fan running or Humidification stopped can be set as required In cabinet water overflow alarm action Set this parameter to Shutdown Inactivity Only indoor fan running Humidifier stop...

Page 276: ...Max value or Min value of the temperatures collected by each sensor Temperature setpoint After Temperature and humidity control type and the temperature value under this type are set the device performs cooling or heating based on the settings Humidity setpoint After Temperature and humidity control type and the humidity value under this type are set the device performs humidifying or dehumidifyin...

Page 277: ...ttings Spray System Spray pump rotation period Specifies spray pump rotation period Antifreeze temperature Specifies the lowest temperature for the spray system Settings System Settings Exhaust Fan Min exhaust fan speed Specifies the minimum rotational speed of the exhaust fan Max exhaust fan speed Specifies the maximum rotational speed of the exhaust fan Exhaust air damper Exhaust air damper can ...

Page 278: ...ibration value of each sensor when the detected temperature or humidity varies from the practical value For example if the detected return air temperature is 1 C lower than that detected by other devices set the calibration value to 1 C Return air temp calibration value Return air humidity calibration value Outdoor intake air temperature calibration value FusionCol8000 E240 Modular Indirect Evapor...

Page 279: ...ir temperature calibration value Paral comp sys discharge pres calibration value Paral comp sys suction pres calibration value Paral comp sys suction temp calibration value Paral comp sys liquid pipe temp calibration value FusionCol8000 E240 Modular Indirect Evaporative Cooling System User Manual C Parameter Description Issue 02 2021 04 15 Copyright Huawei Technologies Co Ltd 270 ...

Page 280: ...ion NTC sensor 9 Vapor liquid separator 10 Needle valve 11 Evaporator air intake NTC sensor 12 EEV 13 Liquid pipe NTC sensor 14 Filter dryer 15 Condenser 16 Condenser intake air NTC sensor 17 Evaporator 18 Oil return filter 19 Oil return capillary FusionCol8000 E240 Modular Indirect Evaporative Cooling System User Manual D Cooling System Layout Issue 02 2021 04 15 Copyright Huawei Technologies Co ...

Page 281: ...l Diagrams Figure E 1 Electrical conceptual diagram 1 FusionCol8000 E240 Modular Indirect Evaporative Cooling System User Manual E Electrical Conceptual Diagrams Issue 02 2021 04 15 Copyright Huawei Technologies Co Ltd 272 ...

Page 282: ...e E 2 Electrical conceptual diagram 2 FusionCol8000 E240 Modular Indirect Evaporative Cooling System User Manual E Electrical Conceptual Diagrams Issue 02 2021 04 15 Copyright Huawei Technologies Co Ltd 273 ...

Page 283: ...e E 3 Electrical conceptual diagram 3 FusionCol8000 E240 Modular Indirect Evaporative Cooling System User Manual E Electrical Conceptual Diagrams Issue 02 2021 04 15 Copyright Huawei Technologies Co Ltd 274 ...

Page 284: ...e E 4 Electrical conceptual diagram 4 FusionCol8000 E240 Modular Indirect Evaporative Cooling System User Manual E Electrical Conceptual Diagrams Issue 02 2021 04 15 Copyright Huawei Technologies Co Ltd 275 ...

Page 285: ...e E 5 Electrical conceptual diagram 5 FusionCol8000 E240 Modular Indirect Evaporative Cooling System User Manual E Electrical Conceptual Diagrams Issue 02 2021 04 15 Copyright Huawei Technologies Co Ltd 276 ...

Page 286: ...e E 6 Electrical conceptual diagram 6 FusionCol8000 E240 Modular Indirect Evaporative Cooling System User Manual E Electrical Conceptual Diagrams Issue 02 2021 04 15 Copyright Huawei Technologies Co Ltd 277 ...

Page 287: ...e E 7 Electrical conceptual diagram 7 FusionCol8000 E240 Modular Indirect Evaporative Cooling System User Manual E Electrical Conceptual Diagrams Issue 02 2021 04 15 Copyright Huawei Technologies Co Ltd 278 ...

Page 288: ...e E 8 Electrical conceptual diagram 8 FusionCol8000 E240 Modular Indirect Evaporative Cooling System User Manual E Electrical Conceptual Diagrams Issue 02 2021 04 15 Copyright Huawei Technologies Co Ltd 279 ...

Page 289: ...e Platform Figure F 1 Air filter maintenance platform FusionCol8000 E240 Modular Indirect Evaporative Cooling System User Manual F Air filter Maintenance Platform Issue 02 2021 04 15 Copyright Huawei Technologies Co Ltd 280 ...

Page 290: ...rved on the device G 1 Physical Ports of Air Vents Figure G 1 Dimensions of an indoor air supply vent unit mm FusionCol8000 E240 Modular Indirect Evaporative Cooling System User Manual G Physical Ports Building Scenario Issue 02 2021 04 15 Copyright Huawei Technologies Co Ltd 281 ...

Page 291: ...ke vent unit mm Figure G 3 Dimensions of an indoor air return vent unit mm FusionCol8000 E240 Modular Indirect Evaporative Cooling System User Manual G Physical Ports Building Scenario Issue 02 2021 04 15 Copyright Huawei Technologies Co Ltd 282 ...

Page 292: ... unit mm G 2 Physical Ports of Pipes Figure G 5 Dimensions of a water pipe unit mm FusionCol8000 E240 Modular Indirect Evaporative Cooling System User Manual G Physical Ports Building Scenario Issue 02 2021 04 15 Copyright Huawei Technologies Co Ltd 283 ...

Page 293: ...rol box front view 1 Active power switch QF1 2 Standby power switch QF2 3 Reserved terminal block and water sensor port 4 Transformer TC 1 reserved FusionCol8000 E240 Modular Indirect Evaporative Cooling System User Manual G Physical Ports Building Scenario Issue 02 2021 04 15 Copyright Huawei Technologies Co Ltd 284 ...

Page 294: ...side view unit mm Table G 1 Physical ports of cables Type Item Specifications Port Quantity Power cable port Active power supply AC1 input L1 1 AC1 input L2 1 AC1 input L3 1 PE 1 Standby power supply AC2 input L1 1 AC2 input L2 1 AC2 input L3 1 PE 1 FusionCol8000 E240 Modular Indirect Evaporative Cooling System User Manual G Physical Ports Building Scenario Issue 02 2021 04 15 Copyright Huawei Tec...

Page 295: ...ure and humidity T H sensor cascading supported RS485 1 Smoke sensor port Input 1 Water sensor port Input 1 Supply air damper port 24 V DC power supply voltage range 0 10 V 1 Exhaust air damper port 1 Return air damper port 1 FusionCol8000 E240 Modular Indirect Evaporative Cooling System User Manual G Physical Ports Building Scenario Issue 02 2021 04 15 Copyright Huawei Technologies Co Ltd 286 ...

Page 296: ...ed on the device H 1 Physical Ports of Air Vents Figure H 1 Dimensions of an indoor air supply vent end unit mm FusionCol8000 E240 Modular Indirect Evaporative Cooling System User Manual H Physical Ports FDC Scenario Issue 02 2021 04 15 Copyright Huawei Technologies Co Ltd 287 ...

Page 297: ... vent end unit mm Figure H 3 Dimensions of an indoor air return vent side unit mm FusionCol8000 E240 Modular Indirect Evaporative Cooling System User Manual H Physical Ports FDC Scenario Issue 02 2021 04 15 Copyright Huawei Technologies Co Ltd 288 ...

Page 298: ... vent end unit mm Figure H 5 Dimensions of an outdoor air exhaust vent top unit mm FusionCol8000 E240 Modular Indirect Evaporative Cooling System User Manual H Physical Ports FDC Scenario Issue 02 2021 04 15 Copyright Huawei Technologies Co Ltd 289 ...

Page 299: ...hysical Ports of Pipes Figure H 7 Dimensions of a water refill pipe side unit mm 1 Water tank refill pipe FusionCol8000 E240 Modular Indirect Evaporative Cooling System User Manual H Physical Ports FDC Scenario Issue 02 2021 04 15 Copyright Huawei Technologies Co Ltd 290 ...

Page 300: ... tank refill pipe G 3 4 inch internal thread connector 1 Condensate water pan drainpipe of the evaporator G 3 4 inch internal thread connector 1 Water tank drainpipe G 1 1 2 inch internal thread connector 1 Condensate water pan drainpipe G 1 inch internal thread connector 1 FusionCol8000 E240 Modular Indirect Evaporative Cooling System User Manual H Physical Ports FDC Scenario Issue 02 2021 04 15 ...

Page 301: ...ensor port 4 Transformer TC 1 reserved Figure H 10 Dimensions of cable holes on a power distribution box bottom view unit mm 1 Primary power cable hole 2 Backup power cable hole 3 Reserved customer signal cable hole FusionCol8000 E240 Modular Indirect Evaporative Cooling System User Manual H Physical Ports FDC Scenario Issue 02 2021 04 15 Copyright Huawei Technologies Co Ltd 292 ...

Page 302: ...s Port Quantity Power cable port Primary power supply AC1 input L1 1 AC1 input L2 1 AC1 input L3 1 PE 1 Backup power supply AC2 input L1 1 AC2 input L2 1 AC2 input L3 1 PE 1 Teamwork control monitoring external reserved ports Monitoring system RS485 FE 1 Teamwork CAN 2 FE 2 Remote startup shutdown DI 1 Common alarm DO 2 FusionCol8000 E240 Modular Indirect Evaporative Cooling System User Manual H P...

Page 303: ...dity T H sensor cascading supported RS485 1 Smoke sensor port input 1 Water sensor port input 1 FusionCol8000 E240 Modular Indirect Evaporative Cooling System User Manual H Physical Ports FDC Scenario Issue 02 2021 04 15 Copyright Huawei Technologies Co Ltd 294 ...

Page 304: ...efficient P PSU power supply unit PTC positive temperature coefficient PUE power usage effectiveness R RCCB residual current circuit breaker T FusionCol8000 E240 Modular Indirect Evaporative Cooling System User Manual I Acronyms and Abbreviations Issue 02 2021 04 15 Copyright Huawei Technologies Co Ltd 295 ...

Page 305: ...n film transistor U USB Universal Series Bus FusionCol8000 E240 Modular Indirect Evaporative Cooling System User Manual I Acronyms and Abbreviations Issue 02 2021 04 15 Copyright Huawei Technologies Co Ltd 296 ...