218
HP E8402, E8404A Product Specifications
Appendix A
Output Power Specifications
Total Available and
Usable Power
Peak and Dynamic
Current
Product
Temperature
Available Power
a
90-264VAC
Usable Power
b
110-264VAC
Usable Power
b
90-110VAC
E8402A
0-55
°
C
686 W
500 W
500 W
E8404A
0-55
°
C
1,902 W
1,000 W
950W
a.Sum of voltages times currents. Not always usable due to thermal protection
shutdown.
b.Total output before thermal protection shutdown or safety limitation.
E8402A
E8404A
Voltage
Peak Current,
I
MP
a
,
b
Dynamic Current,
I
MD
a
,
c
Peak Current,
I
MP
a
,
b
Dynamic Current,
I
MD
a
,
c
+5V
50A
5A
90A
9A
+12V
6A
1A
15A
2.5A
-12V
4A
1A
15A
2.5A
+24V
4A
2A
15A
5A
-24V
4A
2A
15A
5A
-5.2V
20A
2A
60A
8A
-2V
10A
1A
30A
5A
a.
Specifications apply at the backplane, 0-55
°
C.
b.
IMP = Rated mainframe peak DC output current as defined by the VXIbus Specification.
c.
IMD = Rated mainframe peak-to-peak dynamic current as defined in the VXIbus Specification by
a current vs. frequency curve.