Programming the Enhanced Monitor
113
Chapter 3
STATus:QUEStionable:TEMPerature:LEVel?
<slot>[,MIN|MAX]
The
STATus:QUEStionable:TEMPerature:LEVel?
query returns three integers
representing the present temperatures, in degrees Celsius, in the mainframe.
Parameters
Returned Data
Comments
•
When querying AMBient, MIN, or MAX temperature, the same temperature is
returned in all three values. The measurements returned for any <slot> are the
last measurements taken. In normal operation, this is a measurement taken
during the last 2 seconds. If a *TST? or CAL? are being performed, the
measurements returned by this query are the last measurements taken before
the long operation started. If the mainframe power is off, the measurements
returned by this query are the last measurements taken before power went
down.
•
Refer to “Setting Enhanced Monitor Limits” on page 37 for information on
selecting and using temperature limits.
Reset Condition
*RST does not affect the temperatures. It can affect the maximums and minimums
if a limit was set and not saved with the
SYSTem:NVSave
command.
Name
Type
Range
Default
Description
<
slot>
enum. OUT0…OUT12,
DELTa0…DELTa12
AMBient
none
Last measured exhaust temperature
for slots 0 - slot 12
Last measured temperature change
above the ambient temperature for
slot0 - slot 12
Last measured entrance air
temperature
optional
parameter
enum. MIN, MAX
none
Adding MIN or MAX to the query
returns the present threshold being
used to determine temperature
warnings.
Type
Range
Default
Description
int16, int16, int16
-100 to +100
none
Temperature, in
°
C, from each of the
three sensors: front, middle, rear