60
Honeywell, Issue 9
March 2007
XLS80e Fire Alarm Control Panels
THESE RULES CAN BE USED:
IF TWO INPUTS TRY TO ACTIVATE THE SAME
OUTPUT IN DIFFERENT MODES, THE OUTPUT
MODE IS SET ACCORDING TO TWO RULES:
Decision Conflict
Decision Conflict occurs when two Control
Matrix entries try to set an output in two
different modes at the same time. Precedence
rules then apply.
Use of Decision Conflict in Configuration
Example:
Configure two Control Matrix entries
with identical input categories. One output is
immediate pulse, the other delayed steady:
a. The pulse mode is
immediate
, so will have
priority over the
delayed
steady mode.
b. At the end of the delay, the
steady
mode
will have priority over the
pulse
mode.
The output is therefore in pulse mode for the
delay time, then it changes to steady mode.