78
Honeywell, Issue 9
March 2007
XLS80e Fire Alarm Control Panels
7.8.3 Device Selection
All modules that are required to activate a Non-
fire Control Matrix entry must be configured
as type AUX.
The Immediate release switch should be type
MCP or MON.
All modules of type CTRL
must
be set to non-
silenceable so that the panel’s SILENCE/
RESOUND pushbutton does not control the
extinguishant release. Set their open-circuit
supervision OFF.
7.8.4 HOLD Options
The HOLD switch may have one of four effects
on the delay timer. Each effect has a three-
character name:
AHJ - When HOLD is deactivated, the timer
starts again from its configured value.
To configure on XLS80e:
1
Set non-fire to ‘HOLD mode: RE-START
or EXTEND timer’.
2
Leave activation delay at the panel’s default
value.
NYC - When HOLD is deactivated, the timer
starts again from a length of time longer than
its configured value.
To configure on XLS80e:
1
Set non-fire to ‘HOLD mode: RE-START
or EXTEND timer’.
2
Set activation delay to a period longer than
the panel’s default value.
ULI - When HOLD is activated, the timer is
paused at a configured number of seconds
before release. When HOLD is deactivated
the timer restarts from this pause time.
To configure on XLS80e:
1
Set non-fire to ‘HOLD mode: Run timer then
PAUSE’.
2
Ensure the Alarm entries are ‘AUTO
Release’/’Manual Release’.
IRI - As ULI but HOLD switch activity is ignored
if two or more zones are in co-incident alarm.
To configure on XLS80e:
1
Set non-fire to ‘HOLD mode: Run timer then
PAUSE’.
2
Ensure the Alarm entries are ‘AUTO
Release override HOLD’/’Manual Release
override HOLD’.
3
Ensure Alarm entries have the ‘Two or more
Zones COINCIDENCE’ option selected
Control Modules used to
activate the direction
valve and the release
valve MUST be
configured as NON-
SILENCEABLE.