Honeywell, Issue 9
March 2007
XLS80e Fire Alarm Control Panels
3
If 3rd Party is selected, set the protocol
version to match your usage.
4
Set the operating mode to match your
usage.
5
If 3rd Party is selected, select whether the
panel will accept Mute Buzzer, Evacuate,
Silence Sounders, Reset, Test and
Disablement signals from the external
equipment (Controls ENABLED) or not
(Controls DISABLED).
6
Select whether the 3rd party data link is
continuously-monitored (Fault Monitoring
ENABLED - a fault is reported by the panel
if the link fails) or not (Fault Monitoring
DISABLED).
7
Select whether a request by the external
equipment to suspend communications is
subject to a time limit (enter a numeric value
in the given range) or not (enter 0). If a time
limit is entered and the communications are
not restored within that limit, then a fault is
reported by the panel. An option to prevent
logging of Suspend/Resume events is
provided (to reduce XLSnet workload).
8
If the external equipment has an unusually-
slow data delivery rate, it may be necessary
to adjust the incoming data timeout
(otherwise leave at its 1 second default).
11.17 Diagnostic RS232 Port Set-up
This option is for manufacturer’s use only (it
requests access passcode 3B).
FROM PREVIOUS PAGE (3RD PARTY OPTION)
MAKE SELECTION,
THEN
NUMERIC
ENTRY,
THEN
(AT
CONFIRM
PROMPT)
MAKE SELECTION,
THEN
Panel Settings
ISOLATED RS232 Port setup
3rd Party RS232:Incoming Data timeout
(1-20 sec.): 1
EN54
Do not select ENABLED
- some 3rd party signals
may contravene EN54
NUMERIC
ENTRY, THEN
Panel Settings
ISOLATED RS232 Port setup
3rd Party RS232:SUSPEND time limit
(1-300 min.; 0 = no limit): n
1:
2:NOT LOGGED
LOGGED