45
XLS80e Fire Alarm Control Panels
Honeywell, Issue 9
March 2007
5.3
Learn Devices on Loops
This option allows the panel to detect and
automatically configure devices that it finds
already connected to the loops. If the panel
has already been configured, the panel can
amend the details of any installed devices that
do not match the configuration.
By default, all sensors on all loops are learnt,
then all modules on all loops. Smaller ranges
can be selected.
The procedure can be run automatically, or in
manual mode (the system pauses on each new
learnt device).
5.3.1 Starting the Procedure
To start this option:
1
From the Loop Device Configuration menu,
select the Learn Devices on Loops option.
2
Select the loop from which the learn
process is to begin. If you want to learn the
entire system, this should be set to ‘1’.
3
If you want to learn all the devices on the
loop selected in step 2, select SENSOR,
otherwise the panel will begin learning from
the module addresses on the loop.
4
Select the start address. To learn all the
addresses, set this value to ‘1’.
SEE NEXT PAGE
NUMERIC KEYS,
THEN
NUMERIC KEYS,
THEN
Caution - a false indication
of a fully-functional system
is given if the Auto-learn
procedure is used on an
incomplete system.
Input module types are
set to defaults during the
Auto-learn procedure
and may require manual
re-configuration.
Using the defaults through-
out will select the entire
system.