64
Honeywell, Issue 9
March 2007
XLS80e Fire Alarm Control Panels
1
Select one of ‘Cell, Zone or Panel’ (go to
step 2), ‘Specified Individual Device’
(step 7), or ‘Virtual Input Point’ (step 10).
2
If ‘Cell, Zone or Panel’ is selected, you are
then prompted for a specific panel (Step 3)
or ANY panel for an input.
3
If ‘Input from SPECIFIED Panel’ is selected,
you are asked to specify a particular panel
number. The * and initial cursor position
indicate the local panel. The * remains fixed,
the cursor is movable. Select a panel from
the list.
4
If the current panel is selected specify
whether the Control matrix rule is to apply
for Normal or Fallback network operation.
5
Select ZONE or PANEL or CELL.
Note:
If no cells are configured (Sections
5.1.2.2/5.1.4.2) the ZONE or PANEL/
CELL selection screen is bypassed.
SELECTION OF EITHER NETWORK OPTION
AT STEP 4 OR IF ‘ANY’ WAS SELECTED AT
STEP 2, DISPLAYS THE FOLLOWING
SCREENS:
Zone Coincidence
6
These options are provided if the input is
from Any Zone or from a range of zones.
They are intended for use with the
Extinguishing System, although are
available for any ‘Alarm’ input. Select the
required option. SINGLE Zone and 2 Zones
are always available; the remaining options
are only displayed if they are configured in
the panel settings (
Section 11.21
). In the
illustration, ‘n’, ‘p’ and ‘q’ each represent a
number in the range 3-99.
Multiple zone co-incidence: for the
Control Matrix entry to be valid,
the number of co-incident zones
must not exceed the chosen zone
range.
The use of zone coincidence and
restricted-by-type in the same
Control Matrix entry is not
supported.
IF SPECIFIED PANEL:
IF CELL, ZONE OR
PANEL:
Create New Control Matrix Entry
Define Matrix INPUT: Please select:-
ALARM
1:
2:Specified Individual Device
3:Virtual Input Point
Cell, Zone or Panel