XLS80e Fire Alarm Control Panels
11.12 Relay Circuits SILENCE Option
This setting determines whether the internal
sounder/relay circuits 3 and 4, if configured in
hardware as relay circuits, are switched off
when the SILENCE/RESOUND pushbutton is
operated to silence the sounders.
Note:
For loop-based modules, refer to the Module
SILENCE Options (
Section 5.1.4.8
).
Select the required option and confirm the
change.
11.13 Mains/PSU Fault Delays
This setting allows the time delay between
mains failure and fault indication to be changed
(would normally only be altered if the system
suffers from frequent mains failures of more
than a few seconds).
SILENCE OPTION TAKES EFFECT
MAKE SELECTION
(AT CONFIRM
PROMPT)
EN54-4: 5.4
Mains fail delay
MUST NOT exceed
30 minutes.
NUMERIC
ENTRY, THEN
(IF TOTAL IS LESS THAN 5 MINUTES, ENTER
THE NUMBER OF SECONDS)
NUMERIC
ENTRY,
THEN
(AT
CONFIRM
PROMPT)
DELAY TAKES EFFECT
1
Enter the number of hours (max. 5).
2
Enter the number of minutes.
3
If applicable, enter the number of seconds.
Note:
A second item ‘PSU FAULT additional
delay’ may be displayed to allow a time
delay for fault messages to be set, and
thus suppress spurious messages. This
item is not available unless the type of
power supply fitted requires it.
4
Confirm the changes.