47
XLS80e Fire Alarm Control Panels
Honeywell, Issue 9
March 2007
5.3.2 Run in Auto-Learn Mode
If you select this option, then:
Note
: Steps 1 to 3 are omitted if only sensors
were selected in the procedure of
Section 5.3.1
. The choices made in these
steps are only used for new or changed
modules, not for unchanged modules that
have already been configured.
1
Select whether MULTI devices of type
Acclimate are automatically configured for
Thermal Mode by Zone operation
(
Section 5.1.3
) or not. The ‘Thermal Mode
by Zone’ option in the device configuration
menu is then set automatically to ‘Yes’.
2
Select a logical device type with which any
MMX modules found during the learn
procedure will be configured.
3
Select a logical device type with which any
CMX modules found during the learn
procedure will be configured.
4
Select the action to be taken if an
unterminated module (or one with broken
tabs) is found during the learn procedure:
a. WARN. The learn procedure halts if an
unterminated module is found.
b. REJECT. The module is not learnt.
c. ACCEPT. Options are provided to either
‘accept, monitor termination’ (the module
is learnt and is configured with its open-
circuit supervision set to ON) or ‘accept as
unterminated’ (module is learnt with open-
circuit supervision set to OFF - in this case
a warning message is displayed and you
must confirm that you want this option).
MAKE
SELECTION
MAKE
SELECTION
SEE NEXT
PAGE
MAKE
SELECTION
Auto-learn devices on loops:
Start from loop 1 Sensor 1
End at loop 1 Sensor 99
Action on Acclimate (MULTI) sensors:
1:
2:ENABLE Thermal Mode Select by ZONE
DISABLE Thermal Mode Select by ZONE
MAKE
SELECTION